Add to Cart
230kv Xlpe Insulated Optical Fiber High Voltage Cable Underground Cable
1. The cross-linkage PE insulated and wrinkled aluminum wrapper waterproof PVC sheathed power cable.
Type | YJLW02,YJLLW02 |
Specification | 240mm2~3000mm2 |
Voltage | 110~220KV |
Usage | Suitable for damp areas and the places with a lower underground water level and to be used underground, in tunnels or pipes. Such cables bear a bigger pulling force and pressure. |
2. The cross-linkage PE insulated and wrinkled aluminum wrapper waterproof PE sheathed power cable.
Type | YJLW03,YJLLW03 |
Specification | 240mm2~3000mm2 |
Voltage | 110~220KV |
Usage | Suitable for the places with a higher underground water level and to be used underground, in the tunnels or pipes. Such cables bear a bigger pulling force and pressure. |
Cable type Bending diameter | Metal sheathed |
After laying | 30D0 |
During laying | 40D0 |
Note: In form, D0 is a real test value to cable’s outer diameter.
The single core cable is required P≤500kg/m.
P=T/R (T is indicated axial traction force; R is indicated radius of bent-wheel), Knowing from above formula, as the traction force is made up by length and weight of cable. So it lets P to applying requirement as above. Then the diameter of bent-wheel should be widened.
Type: YJLW02(or YJLW03) Specifications: 1×240mm2~1×1200mm2 | |||||||
Conductor section mm2 | Conductor diameter mm | Insulator thickness mm | Aluminum wrapper mm | Sheath thickness mm | Cable’s outer diameter mm | kg/km Cable’s weight | |
PVC sheath | PE sheath | ||||||
240 | 18.4 | 19.0 | 2.0 | 4.5 | 89.9 | 8348 | 7708 |
300 | 20.6 | 18.5 | 2.0 | 4.5 | 91.1 | 8990 | 8341 |
400 | 23.8 | 17.5 | 2.0 | 4.5 | 92.3 | 9731 | 9073 |
500 | 26.6 | 17.0 | 2.0 | 4.5 | 94.5 | 10882 | 10208 |
630 | 30.0 | 16.5 | 2.0 | 4.5 | 96.9 | 12352 | 11660 |
800 | 34.0 | 16.0 | 2.0 | 4.5 | 99.9 | 14168 | 13454 |
1000 | 38.2 | 16.0 | 2.0 | 4.5 | 105.0 | 16460 | 15708 |
1200 | 42.6 | 16.0 | 2.0 | 4.5 | 109.4 | 18685 | 17900 |
Conductor section mm2 | (Ω/km) Conductor resistance | Capacitance μF/km | Carrier current capacity A | Short circuit current | ||
20℃DC | 90℃AC | Conductor | Metal sheath | |||
240 | 0.0754 | 0.0961 | 0.135 | 543 | 20 | 22 |
300 | 0.0601 | 0.0766 | 0.146 | 597 | 25 | 22 |
400 | 0.0470 | 0.0599 | 0.165 | 657 | 33 | 22 |
500 | 0.0366 | 0.0467 | 0.182 | 718 | 41 | 23 |
630 | 0.0283 | 0.0361 | 0.201 | 779 | 52 | 24 |
800 | 0.0221 | 0.0282 | 0.223 | 837 | 66 | 25 |
1000 | 0.0176 | 0.0224 | 0.246 | 914 | 83 | 26 |
1200 | 0.0151 | 0.0193 | 0.266 | 962 | 99 | 27 |
Note: Current carrier capacity is made up by laying in soil abreast. The axial distances between cables are 200mm. Soil temperature is 25℃. The working temperature of cable is 90℃. The coefficient of soil heat-resistance is 1.2km/W.
Type: YJLW02(or YJLW03) Specifications: 1×400mm2~1×2500mm2 | |||||||
Conductor section mm2 | Conductor diameter mm | Insulator thickness mm | Aluminum wrapper mm | Sheath thickness mm | Cable’s outer diameter mm | kg/km Cable’s weight | |
PVC sheath | PE sheath | ||||||
400 | 23.8 | 27 | 2.4 | 5.0 | 128.7 | 14348 | 13369 |
500 | 26.6 | 27 | 2.4 | 5.0 | 131.5 | 15697 | 14696 |
630 | 30.0 | 26 | 2.4 | 5.0 | 132.8 | 17064 | 16052 |
800 | 34.0 | 25 | 2.5 | 5.0 | 134.9 | 18913 | 17885 |
1000 | 38.2 | 24 | 2.5 | 5.0 | 137.7 | 20966 | 19918 |
1200 | 42.6 | 24 | 2.6 | 5.0 | 142.3 | 23459 | 22372 |
1400 | 46.1 | 24 | 2.6 | 5.0 | 145.8 | 25712 | 24598 |
1600 | 49.2 | 24 | 2.7 | 5.0 | 149.1 | 28039 | 26899 |
1800 | 52.1 | 24 | 2.7 | 5.0 | 152.0 | 30214 | 29050 |
2000 | 55.2 | 24 | 2.8 | 5.0 | 155.3 | 32548 | 31359 |
2200 | 57.5 | 24 | 2.8 | 5.0 | 157.6 | 34643 | 33436 |
2500 | 61.2 | 24 | 2.9 | 5.0 | 161.5 | 37958 | 36719 |
Conductor section mm2 | (Ω/km) Conductor resistance | Capacitance μF/km | Carrier current capacity A | (KA/3S) Short circuit current | ||
20℃DC | 90℃AC | Conductor | Metal sheath | |||
400 | 0.0470 | 0.0613 | 0.120 | 689 | 33 | 46 |
500 | 0.0366 | 0.0485 | 0.127 | 763 | 41 | 47 |
630 | 0.0283 | 0.0384 | 0.139 | 839 | 52 | 48 |
800 | 0.0221 | 0.0311 | 0.153 | 918 | 66 | 51 |
1000 | 0.0176 | 0.0232 | 0.173 | 1014 | 83 | 52 |
1200 | 0.0151 | 0.0201 | 0.182 | 1082 | 99 | 56 |
1400 | 0.0129 | 0.0174 | 0.191 | 1136 | 116 | 58 |
1600 | 0.0113 | 0.0156 | 0.200 | 1192 | 132 | 62 |
1800 | 0.0101 | 0.0142 | 0.208 | 1232 | 149 | 63 |
2000 | 0.0090 | 0.0128 | 0.217 | 1282 | 165 | 67 |
2200 | 0.0083 | 0.0121 | 0.223 | 1310 | 182 | 68 |
2500 | 0.0073 | 0.0110 | 0.233 | 1367 | 206 | 73 |
Note: Current carrier capacity is made up by laying in soil abreast. The axial distance between cables are 200mm. Soil temperature is 25℃. The working temperature of cable is 90℃. The coefficient of soil heat-resistance is 1.2km/W.