High Measurement CT Analyzer / Current Transformer Analyzer KT200
TFT LCD display screen
IEC 60044-1 / IEC60044-6 standard
Voltage Output:0-120 V(AC)
Technical Parameters List
Power Supply Input | AC:85-260 V, 47-63 Hz, 10 A(max.) | Variable Ratio Measurement | Range:1-5000, accuracy: ±0.1% |
Voltage Output | 0-120 V(AC) | Phase Measurement | Accuracy: ±3 min, resolution:0.01 min |
Current Output | 0-5 A(RMS) | Secondary Winding | Range:0.1-10 0 Ω |
Power Output | 0-450 VA, | AC Load Measurement | 0-300 VA |
Current | Range:0-15A(automatic range), Accuracy: ±0.1% | Working Condition | Temperature:-10°C-55°C |
Voltage | Range:0-30 V(automatic range), accuracy: ±0.1% | Dimension and Weight | 360mm×325mm×140mm |
Innovative Design, easy maintenance!
With innovative modularize design, Plug-in frame, self-calibration
function which make maintenance more easy!
1, Consisting of Function modularization design and plug-in frame,
each module contains self-calibration function, plug and play when
change module, easy to maintain for customer.
2, Adopt TFT LCD display screen with clear and beautiful software
interface design, user can operate easily
3, AC/DC current input for wide range only, satisfy all power
supply standard requested.
4, Easy to operate, measure quickly, all test can be done
automatically based on the same connection line type except
overload impedance measurement.
5, Adopt low voltage & variable frequency measurement method,
it can test inflexion voltage up to 30kV transformer as output max
voltage only is 120V and max peak value current is 15A, high
security.
6, Portable design with light weight of 10kg, suitable for field
test of electric power system, manufacturing factory of current
transformer or laboratory to use.
7, High measurement accuracy, resistance accuracy is 0.1%+1mΩ,
phase accuracy±0.05 degree, variable accuracy is ±0.1% (1-5000 ),
variable accuracy is ±0.2%(5000-10000)
8, It can test current transformer according to IEC 60044-1 or
IEC60044-6 standard etc.
9, Complete measurement function, it can test all type current
transformer for secondary overload, secondary loop resistance,
excitation characteristic, transient characteristic, ratio
difference, angle difference and polarity. It can also test exact
limit coefficient(ALF), device security coefficient(FS), secondary
time constant(Ts), remanence coefficient(Kr), transient area
coefficient(Ktd), inflexion voltage, current, level, saturation
inductance, un-saturation inductance, 5% 10% error curve, of
current transformer, hysteresis loop for current transformer, and
evaluate test result according to defined standard.
10. PT Test
As for those inductive PT based on the definition of
GB1207-2006(IEC60044-2), KT200 CT/PT Analyzer can also test them.
KT200 CT/PT Analyzer can do variable ratio, polarity and secondary
winding excitation test of inductive PT.