Three Phase Modular UPS 10-300KVA for Data Center / Telecom / Servers , CE Listed

Brand Name:SOROTEC
Certification:CE
Model Number:MPS9335C 10 - 300KVA
Minimum Order Quantity:1PCS (Sample are Available)
Delivery Time:Within 15-30days after receiving your 30% TT deposit
Payment Terms:30% TT in advance, the balance before shipping
Contact Now

Add to Cart

Active Member
Location: Shenzhen Guangdong
Address: Building B22 , Tantou West Industrial Park , Songgang Town , Bao'an District ,Shenzhen ,518105 P.R.CHINA
Supplier`s last login times: within 1 hours
Product Details Company Profile
Product Details

SOROTEC Modular UPS 3Phase MPS9335C 10-300KVA for Data Center / Telecom / Servers


MPS9335C Series Modular UPS 10-300KVA

Support 4 units UPS for parallel working/Output power factor is 0.9/3Ph in and 3Ph out/Online capacity expansion and maintenance/Extra LCD display 13 type languages/Extra wide input voltage and frequency ranges/widely used to provide reliable and long time backup power supply for IDC(Internet Data Center), computing center, ISP (Internet Service Provider ),Telecom,Finance bank and securities, Tax, hospital system, industrial automation, precision equipment, etc.


Key Features:


1. input THDi<3%,Efficiency > 96% at 50%-75% rated load,


2.Easy-to-install,Easy-to-maintain,Easy-to-modify


3. 6-inch extra large LCD that can display 13 language


4.Provide large LCD touch screen (optional)


5.Each UPS modules provide 4.5KW charge capacity. equivalent to 10 to 12A


6.On-Line Double Conversion, fully isolating the influences of power grid pollution


7.Advanced DSP full digital control technologies


8.Advanced distributed active parallel technology realizes parallel operation of 4 UPS units


Technical Specifications of Modular UPS, MPS9335 10-300KVA:

Model

MPS9335 10-300KVA
Capacity10-300KVA
Main input
Input voltage380V/400V/415AC(Optional South America 208v)
Input Frequency Range50/60Hz
Power FactorFull load>0.99 ,Half load >0. 98
THDiTHDi <3%
Input power soft-start fantion5-30s settable
Input Voltage Ranges228V-476V-20%- +25% Full load linear derating at -25% - -40%; can take 70% load at -40%
Frequency Range40-70Hz
Battery
Battery Voltage±240VDC(Default),12V Battery30-40pcs can be choose
Charge Voltage accuracy± 1%
Bypass
Bypass Input voltage380/400/415VAC 3-phase 4-wire
Voltage RangesDefault value is -20%-+15%, -40%, -30%, -10% - +10%, other ranges can be set via software
Overload Capacity150%,long term operation,150%<load<180%,more than 1 hour ,load>1000% 100ms
Output
Inverter Output Voltage380/400/415VAC 3-phase 4-wire
Voltage Accuracy± 0.5%(balanced load), ± 1% (unbalanced load)
THDiTHD<1%(linear load), THD<3%(nonlinear load)
Power Factor0.9
Three Phase Angle accuracy120°c ± 0.5°c
Current Crest Ratio3:1
Overload Capacity110%1h,125%10mins,150%1mins,>150%200ms
Transfer Time0ms,15ms(ECO Mode)
System
Frequency50Hz/60Hz (Settable)
Mains synchronization range±2Hz(Default value) adjustable with step of 0.5Hz within range of +/- 0.5Hz - 3Hz
Protection LevelIP20
Communication PortsRS232,RS485,dry contact,SNMP card,EPO,generator port
System efficiency> 96% at load above 50%, >95% at load above 25%
Operation Temperature0-40 °c
Storage Temperature-25 °c -70 °c (without battery)
Humidity0-95%(no-condensing)
Noise(dB)55-62dB,Adjusted with load
5 module cabinetmodule :RMS050/10, RMS100/20, RMS150/30150KG
10 module cabinetmodule :RMS100/10, RMS200/20, RMS300/30150KG
module :PM1010KVA power module :20KG
Weightmodule :PM2020KVA power module :21KG
module :PM3030KVA power module :32KG
Dimendion(W XD XH)mm5 module cabinet600X1400X850
10 module cabinet600X2070X850
power module440X132X660(10KVA/20KVA/30KVA)