SIEMENS LEAD BATTERY PACK 6EP1935-6ME21

describe
SITOP BATTERY MODULE/24V/7AH
SITOP battery module 24 V/7 Ah with maintenance free sealed lead
batteries for SITOP DC UPS module 6 A, 15 A and 40 A *Ex approval no
longer available*
Charging current charging voltage
end-of-charge voltage at DC
● at -10 °C recommended29 V
● at 0 °C recommended28.4 V
● at 10 °C recommended27.8 V
● at 20 °C recommended27.3 V
● at 30 °C recommended26.8 V
● at 40 °C recommended26.6 V
● at 50 °C recommended26.3 V
Output
charging current maximum1.75 A
output voltage at DC rated value24 V
Safety
design of short-circuit protectionBattery fuse 20 A/32 V (solid-state circuitry blade-type fuse + support)
design of the overload protectionValve control
Safety
operating resource protection classClass III
protection classIP IP00
Approvals
certificate of suitability
● CE markingYes
● UL approvalYes
● as approval for USAcURus-Recognized (UL 1778, CSA C22.2 No. 107.1), File E219627
● cCSAus, Class 1, Division 2No
● ATEXNo
certificate of suitability
● EAC approvalYes
● shipbuilding approvalYes
shipbuilding approvalABS, DNV GL
Marine classification association
● American Bureau of Shipping Europe Ltd. (ABS)Yes
● DNV GLYes
environmental conditions
Operating data noteFor storage, mounting and operation of lead-acid batteries, the relevant
DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part
2/EN 50272-2) must be observed. You must ensure that the battery site
is sufficiently ventilated. Possible sources of ignition must be at least 50
cm away.
ambient temperature
● during operation-15 ... +50 °C
● during transport -20 ... +50 °C
● during storage -20 ... +50 °C
relative temporary capacity loss at 20 °C in a month
typical
3%
Service life
service life of energy storage
● typicalcapacity falls to 80 % of original capacity (according to EUROBAT)
● at 20 °C typical4 a
● at 30 °C typical2 a
● at 40 °C typical1 a
● at 50 °C typical0.5 a
ambient temperature during storageAlong with the storage and operating temperature, other factors such as
the duration of the storage period and the charge status during storage
have a decisive influence on the possible useful life. Batteries should
therefore be stored as briefly as possible, always fully charged, and
within the temperature range 0 to +20 °C.
Mechanics
type of electrical connectionspring-loaded terminals
● for power supply unit1 screw terminal each for 0.08 ... 4 mm² for + BAT and - BAT
product component includedAccessories pack with solid-state circuitry fuse 20 A and 30 A
width of the enclosure186 mm
height of the enclosure168 mm
depth of the enclosure121 mm
installation width206 mm
mounting height188 mm
fastening method
● wall mountingYes
● standard rail mountingNO
● S7 rail mountingNo
fastening methodcan be screwed onto flat surface (keyhole mounting for hooking in to M4
screws)
net weight6 kg
number of cells12
battery capacity7 A·h