ECO Series DC UPS


Main Features:
19inch,2U and 3U Rack mount
High frewuency and online double conversion
Wide input voltage (110-285Vac or 65-148Vac)
Self-diagnosis system at ups start
Digital control technoloy and advanced PFC
Output PF0.8,(0.9 optional)
Lighting and surge protection 1050j
Generator compatible
Smart RS232(USB,SNMP OPTIONAL)
EMI/RFI noise filter
Overview
With true double-conversion design, PowerMaster series provides powerful and overall protection to your sensitive devices. It can accept wider input voltage for harsh environment. It's perfect protection for your precisous servers and workstaiosn.
Specifications  
ModelPMR01SPMR01LPMR02SPMR02LPMR03SPMR03L
Capacity1KVA/0.8kW1KVA/0.8kW2KVA/1.6kW2KVA/1.6kW3KVA/2.4kW3KVA/2.4kW
PhaseSingle
Input voltage
Input PFabove 0.98
THDiless than 5%
Rated voltage220v/230v/240Vac or 110/120/127Vac
Input voltage rangeLow line transfer:176 VAC ± 3% @ 100% load
130 VAC ± 3% @ 50% load
85-148Vac( for 110/120/127Vac)
Low line comback:188VAC ± 3% @ 100% load
142 VAC ± 3% @ 50% load;
100vac±5Vac(110/120/127Vac)
High Line Transfer:286 ± 3%148Vac ± 3%(for 110/120/120vac);
High Line Come Back:271 ± 3%;
145Vac±5Vac(110/120/127Vac)
Rated frequency50/60hz(auto sensing)
Input frequency range46~54 Hz ◎ 50 Hz / 56~64 Hz ◎ 60 Hz
By-pass input
Input voltage range170VAC—270VAC±5V
Frequency following range46~54 Hz ◎ 50 Hz / 56~64 Hz ◎ 60 Hz
Recharge battery
Floating charge voltage28/41VDC55/84/110VDC84/110VDC
Recharging current1A(inbuilt battery)8A1A(Rack batt.case)8A1A(Rack batt.case)8A
Battery
Battery quantity24/36VDC48V/72/96VDC72/96VDC
AC output
Power factor0.8
Phasesingle
Rated voltage220v/230v/240v+/-1.5%
Frequency50/60hz
Frequency stability±0.1HZ(battery inverter)
Voltage stabilitywithin±1.5%( Static)
Crest factor3:1(max)
Wave distortionLinear load less 3%,Non-linear load less 5%;
Over load ability30s when overload is 108%~150%;200ms above 150%;
Transfer time0ms
Alarm
AC abnomalAlarm every 4 seconds
Battery low voltageKeep alarm every 1 second
OverloadKeep alarm every 0.5 second