Add to Cart
HQ-M series modular UPS, configured with online dual transformation topology, provides reliable power supply for loads under different power grid conditions. With full modular design, the capacity of a single HQ-M rack ranges from 20 to 300 KVA and an expanded capacity up to 1200KVA with maximum 4 systems in parallel can be achieved. Easy capacity expansion and convenient maintenance can minimize customers’ total cost of ownership and greatly improve the usability. It is the ideal selection for medium and large scaled data rooms.
Application Scenarios: data centers, disaster tolerance centers, communication network management centers, hub buildings.
HQ-M Series Modular UPS (20KVA-1200KVA)
Features of HQ-M Series Modular UPS Products
Reliable
User-friendly
Energy-saving
Environmental-friendly
Technical Specifications of HQ-M Series Modular UPS
Model | HQ-M90 | HQ-M180 | HQ-M300 |
Max. number of power modules for single rack | 3 | 6 | 10 |
Optional power modules (KVA) | 15/20/25/30 | ||
Number of racks in parallel | Max. 4 racks connected in parallel | ||
Mains AC input | |||
Input wiring | 3 phase + N wire + ground wire | ||
Rated voltage | 380/400/415Vac | ||
Rated frequency | 50/60Hz | ||
Power factor | >0.99 | ||
Harmonic distortion of input current | THDi<3% for linear load;THDi<5% for nonlinear load | ||
Voltage range | 208-480Vac | ||
Frequency range | 40-70HZ | ||
Bypass input | |||
Voltage | Rated voltage: 380/400/415Vac; voltage range in default: -20%~+15% (settable) | ||
Frequency | Rated frequency: 50/60Hz; frequency range: settable | ||
Overload capacity | 110% overload for long-time operating; 1000% overload for 100 milliseconds | ||
Battery | |||
Battery type | Standard configuration: lead-acid batteries; also compatible with lithium iron batteries | ||
Battery voltage | 360-480Vdc (The number of batteries are settable from 30-40; 36 batteries in default) | ||
Charging power | 15% power supply module power | ||
Charging voltage accuracy | ±1.0% | ||
Temperature compensation | 3mV/℃/cell in default; settable from 0 to 5 mV/℃/cell, or forbidden | ||
Ripple voltage | ≤1.414% | ||
Ripple current effective value | ≤5% | ||
Inverter output | |||
Output power factor | 0.9/1.0 | ||
Output voltage | 380V/400V/415V(line voltage) | ||
Voltage accuracy | <±1.0%@steady;<±5.0%@transient | ||
Output frequency | 50/60Hz | ||
Frequency accuracy | ±0.1% | ||
Frequency tracking range | ±3Hz | ||
Total harmonic voltage distortion | THDu≤2%(100% linear load), THDu≤4%(100% nonlinear load) | ||
Three-phase phase accuracy | 120°±0.5° | ||
Peak ratio | 3:1 | ||
Overload capacity | Time to invert to bypass circuit: 110% overload 60 minutes; 125% overload 10 minutes; 150% overload 1 minute; over 150% overload 200 milliseconds | ||
System | |||
System efficiency | Up to 96%@dual switching mode; up to 99%@ECO mode | ||
Displayer | LCN + LED + control panel | ||
Noise (1 meter right ahead) | <55dB | ||
Standards applicable | Safety Standard: IEC52040-1-1; electromagnetic compatibility: IEC62040-2; Design and testing: IEC62040-3 | ||
IP grade | IP20 | ||
Feeder protection | Standard configuration: disconnecting switch; optional: fuse | ||
Communication function | RS232/ RS485/ Modbus/SNMP/programmable dry contact | ||
Optional components | SNMP, extensible dry contact card, dust screen, lightning protection module, LBS wires, earthquake proof component, temperature and humidity sensor | ||
Environment | |||
Operating temperature | 0~40 ℃ | ||
Storage temperature | -40℃~70℃ | ||
Relative humidity | 0~95% (no condensation) | ||
Altitude | 0-1000 meters with no power derating; above 1000 meters, derating by 1% for each 100-meter increase. | ||
Mechanical Properties | |||
System dimension W*D*H (mm) | 600*995*1200 | 600*995*1600 | 600*995*2000 |
System weight (kg) | 210 | 360 | 595 |
Color | Black is the default color, with other colors available |
Module Parameters
Module Model | CM10 | CM15 | CM20 | CM25 | CM30 | CMS-STS |
Mechanical property | 10kVA power module | 15kVA power module | 20kVA power module | 25kVA power module | 30kVA power module | Bypass circuit module |
Mechanical dimension(W*D*H) | 440*660*88mm | 440*660*88mm | 440*660*88mm | 440*660*88mm | 440*660*88mm | 440*575*130mm |
Net weight | 26.5kg | 26.5kg | 26.5kg | 31.5kg | 36.5kg | 23kg |
Color | Black is the default color, with other colors available | |||||
IP grade | IP20 |
* The above specifications are only for reference and subject to change without prior notice, the specific kind shall prevail.