Add to Cart
Medical Online Low Frequency UPS , Double Conversion 100KVA To 800KVA
Introduction: POWER EXCELLET (Ⅱ) is upgraded DSP controlled Online LF UPS with output isolation transformer. It can be your perfect large capacity power shield for your critical and industrial load.
Perfect Applications:Petroleum&chemical industry, metallurgy, nuclear power, electric power, industrial manufacturing, rail transit &high way tunnal lighting , military industry, medical treatment, IDC data center, marine port &dock ect...
QUALITY POWER SUPPLY
HRD PE(II)series is an On-Line double conversion (VFI) UPS with
isolation output transformer, unit capacity from 10KVA to 400KVA.
It is immune to the interferences on the electric power supply line
as it has special input and output filters. World leading DSP
technology, with high speed DSP processor are adopted to guarantee
system’s high stability and giving stable output power supply for
all kinds of harsh load.
PERFECT APPLICAITON: Middle and large data center, Telecom, Finance, Traffic, Defense, Medical, Education, Energy, Manufacture, Industry, etc.
MAXIMUM RELIABILITY
MTBF >200,000h.
The advanced DSP technology appliance considerably improves
reliability, since a reduction in electronic components lowers the
likelihood of breakdowns. Digital control is provided by the
microprocessor that, in the PV(II) series controls all the internal
parameters, thus increasing reliability and performance. In
parallel connections, digital control ensures balance of the
currents, which generally change over time due to phenomena such as
vibrations and temperature, between the UPS units and the exchange
of information with no need for manual tuning. PV(II) has been
designed so that it can be connected in parallel even after the
installation of the first unit. The power availability can be
increased thanks to various configurations available such as the
parallel configuration, the Dual Bus function and the Dynamic Dual
Bus system.
HIGH SPEED DSP PROCESSOR: Ensuring the operation more faster and more stable
OUTPUT 100% UNBALANCE LOAD
The UPS can accept 3phase 100% unbalance load to satisfy kinds of
load configuration.
ECO function: under good power condition, UPS can work in ECO mode, efficiency reach 98%, green and energy saving;
UPS FOR INDUSTRIAL LOADS
PV(II) series with its strong overload capability, output galvanic
isolation and low harmonic current distortion, is the ideal
solution for industrial applications.
Thanks to the high battery current, PV(II) Series is suitable to work with large battery banks as it can guarantee recharging in 10 hours as recommended by the battery manufacturer.
OPERATING FLEXIBILITY:All power ratings of the PV(II) series can also be used as Frequency Converters 50 to 60 Hz and vice versa.
COLORFUL MULTIFUCTIONAL PANEL
The 7 inch colorful multifunctional panel allows easy and humanized
operation of the UPS. It gives access to the most important
parameters: status and alarms, control commands, input, output,
battery measurements (power, current, voltage, frequency and
temperature) and settings. The PE(II) series’ diagnostics system
includes up to 128 alarms or messages allowing precise and detailed
identification of any event.
Advanced Battery Management (ABM)
Optimal battery management includes:
MAXIMUM SAFETY FOR PERSONNEL
The back feed protection device prevents any voltage back feed in
the upstream distribution board, thus ensuring the safety of the
maintenance personnel.
FULL FRONT ACCESS AND CONVENIENT CABLE CONNECTION
Full frontal access is for all power and electronic components,
which reduces the floor space required and consequently reduces the
installation costs.
Configured with top and bottom cable connection
PERFECT HUMAN-MACHINE COMMUNICATION
UPS Monitor software displays the most important information such
as the input and output voltage, the load applied, the remaining
back-up time, etc., in the form of bar graphs. The software is able
to provide information even in the event of a failure, in support
of the fault diagnostics. The UPS Monitor software can be used to
program the automatic shutdown of all open systems in the event of
a prolonged black out. PV(II) can also operate with a network agent
for applications on LAN or WAN networks.
The UPS contains the following hardware interfaces:
ADVANCED PARALLEL
Maximum parallel up to 8 units and share the common battery
pack.10-100kva parallel can be with parallel card only ;
120kva-400kva, parallel card with weaver reactance and different
capacity UPS can be also be parallel;
DYNAMIC DUAL BUS SYSTEM
Two independent systems set in Dual Bus Configuration can be merged
together at any time for system expansion or maintenance. This
provides a lot of flexibility in your installation in case of
maintenance or when it is necessary to change the redundancy level
of both systems.
EVENT LOG: 10000 historical events can be saved, which is easy for tracing UPS operation status and useful for maintenance
PE II series is a fully DSP controlled high-level industry UPS with capacity up to 800kVA.
Based on nowadays the most advanced DSP(TI 2833X CPU), MCU, CPLD ect ,and more than 20nos leading innovative technology ,this UPS has become a perfect robust and cost-effective power solution, optimizing the minimal operating cost for end users.
Its extremely high reliability can solidly ensure the continuous availability of power and safe operations for all types of critical load.
Fully DSP technology with extremely low cycle current,it can be parallel up to 8 units for redundancy or capacity expanding purpose.
Super reliability and excellent performance based on innovative solution,it definitely ensures your business away from any power problem!
MAIN FEATURES:
3.Communication interface:
Specification:
Capacity | 100kVA | 120kVA | 160kVA | 200kVA | 250kVA | 300kVA | 400kVA | ||
90kVA | 108kW | 144kW | 180kW | 225kW | 270kW | 360kW | |||
Input | Wiring connection | Three hase+Ground | |||||||
Nominal yoltage | 380/400/415VAC | ||||||||
Voltage range | 285VAC~498VAC | ||||||||
Frequency | 50/60Hz | ||||||||
Frequency range | 45-65Hz | ||||||||
Soft start | 5-600sec settable | ||||||||
Power factor | 0.95(with input filter) | ||||||||
Bypass | Nominal yoltage | 380/400/415VAC(Three phase+Neutral+Ground) | |||||||
Frequency | 50/60Hz±10% | ||||||||
Voltage range | ±10%,±15%,±20%settable | ||||||||
Output | Nominal voltage | 380/400/415VAC(Three phase+Neutral+Ground) | |||||||
Voltageregulatior | ±1%(balance load),±2%(100%unbalance load) | ||||||||
Power factor | 0.9(1.0 optional) | ||||||||
Dynamic response | ±5%(0~100%load transient | ||||||||
Distortion | <1%(100%linear load), <3%(100%non-linear load) | ||||||||
Transient response | <5ms | ||||||||
Sync.Range | ±2Hz(±0.5—±3Hz settable) | ||||||||
Overload | 105%continue,110%1Hr,125%10min,150%1min | ||||||||
Frequency | ±0.05% | ||||||||
Waveform | Pure sine wave | ||||||||
Efficiency | Inverter mode | Up to 94% | |||||||
ECO mode | 98% | ||||||||
Parallel | N+X | Max 8 units | |||||||
Battery | Configurtation | 12V,32 pieces default(30~34pieces settable) | |||||||
Display | LCD +LED | ||||||||
Physical | Dimension (mm) | Depth | 855 | ||||||
Width(6P) | 890 | 1245 | 1640 | 2265 | |||||
Width (12P) | 1415 | 1770 | 2265 | 2265 | |||||
Height | 1900 | ||||||||
Weight | 6P | 960 | 1075 | 1630 | 2105 | ||||
12P | 1390 | 1672 | 2250 | 2500 | |||||
Environment | Temperature | 0-40℃ | |||||||
Humidity | 0-95%non condensing | ||||||||
Noise()m) | ≤67dB | ||||||||
Communication | RS232/RS485 | Support windows2000/XP/7/Linux/Unix/Mac | |||||||
SNMP(OPTIONAL) | Support remote control through web browser | ||||||||
Standard | Anti-thunder | D grade | |||||||
Safety | IEC60950-1,IEC62040-1-1 | ||||||||
EMC | IEC62040-2,IEC62040-3 |