4P 385V 100kA Surge Protection Device SPD For Lower Voltage Power System
OBV-II100-3 data
Uc(maximum continuous operating voltage) | 385V |
Imax(maximum discharge current) | 10kA |
In(nominal discharge current for class II test) | 20kA |
Up(voltage protection level) | ≤2.5kv |
response time | ≤25ns |
Signal deterioration indication | red: need replace green: work |
Housing Material | Flame retardant plastic |
Housing self-extinguishing class | UL94_V0 |
Temperature range | -40℃~+85℃ |
humidity range | ≤95% |
Elevational | ≤3000m |
Method of connecting wire | multiple (Connect In Parallel ) |
Thread Dimensions | 6mm2~35mm2 |
Mounting method | 35mm standard rail installation |
IP(degree of protection of enclosure) | IP20 |
application standard | GB18802-1;IEC61643-1 |
The classification of the SPD
1. According to the working principle divided:voltage switching
type SPD, voltage limiting type SPD , voltage cobination type SPD
2. According to the use of points : power system surge protection
device, signal system surge protection device
Installation Instructions:
1. Power must be cut off before installation, and live operation is
strictly prohibited
2. It is suggested to connect the fuse or automatic short-circuit
in series at the front end of the lightning protection module
3. Please connect according to the installation diagram, where + is
the positive wire, - is the negative wire, and PE is the ground
wire. Don't make a mistake. After the installation is completed,
close the switch and check whether the working condition is normal
4. Insert the module in place after installation and check whether
the lightning protection module works normally
5. During the use of SPD, it should be regularly monitored and
checked the status of the fault display window. When the fault
display window is red or the remote terminal output an alarm
signal, it indicates that the lightning protection module has
broken down and should be repaired or replaced in time
6. Lightning protection module should be installed in parallel, and
the connecting line should be firm and reliable, and it should be
short, thick and straight