Add to Cart
Automatic Voltage Regulation Small Gasoline Generator 5kva 8kva 10kva
Common faults:
Can't power:
(1) Check and correct wiring errors according to the circuit
diagram.
(2) The excitation windings of the main generator or exciter are
connected incorrectly, resulting in incorrect polarity. It is often
caused by wiring error after replacing the excitation winding. It
should be checked and corrected.
(3) Rotary silicon rectifier element breakdown short circuit,
positive and negative conduction. Use a multimeter to check the
positive and negative resistance of the rectifier element and
replace the damaged element.
(4) The excitation winding of the main generator is broken. Use a
multimeter to check and measure the excitation windings of the main
generator. The resistance is infinite and the excitation line
should be connected.
(5) The winding of the main generator or exciter has a serious
short circuit. The armature winding has a short circuit, which is
generally obvious overheating. The short circuit of the excitation
winding can be determined by the resistance value of its
tributaries. Replace the damaged winding.
The principle of:
A working cycle includes four piston strokes (the so-called piston
stroke refers to the distance between the piston from top dead
center to bottom dead center) : intake stroke, compression stroke,
expansion stroke (work stroke) and exhaust stroke.
Intake stroke:
During this process, the engine's intake valve opens and the
exhaust valve closes. As the piston moves from top dead center to
dead center, the cylinder volume above the piston increases, so
that the pressure in the cylinder drops below the atmospheric
pressure, that is, the vacuum suction is caused in the cylinder, so
that the air is sucked into the cylinder through the intake pipe
and intake valve, and the oil nozzle spray atomized gasoline and
air are fully mixed. At the end of the intake, the gas pressure in
the cylinder is about 0.075-0.09MPa. The temperature of the
combustible mixture in the cylinder has risen to 370-400K.
Compression stroke:
In order to make the combustible mixture inhaled into the cylinder
can burn quickly, so as to produce greater pressure, so that the
engine emits higher power, must be compressed before combustion, so
that its volume is reduced, the density is increased, the
temperature is increased, that is, there is a compression process.
In this process, the intake and exhaust valves are all closed, and
the crankshaft pushes the piston from BDC to DC to move one stroke,
that is, the compression stroke. At this time, the mixture pressure
will increase to 0.6-1.2MPa, and the temperature can reach
600-700K.
specifiCAT-parts-partsion parameter:
Model | SF3600i | SF5600i |
Type | Forced Air-Cooled,1-Cylinder, 4-Stroke,OHV | |
Displacement | HONDA 270 | HONDA 390 |
Rated Power Output | 5.1 KW/3600 RPM | 6.6 KW/3600 RPM |
Max.power Output | 6.2 KW/4200 RPM | 8.2 KW/3600 RPM |
Bore* Stroke(mm) | 77*58 mm | 88*64 mm |
Lgnition System | T.D.I | T.D.I |
Starting System | Recoil Starting/Electric/Remote | Recoil Starting/Electric/Remote |
Recommend Power Using | ||
Fuel Tank Capacity | 13L | 13L |
Fuel Consumption | 450g/kw.h | 299g/kw.h |
Continous Operating Hour | 7 | 8.5 |
Noise( 7 m away) | 59 dba | 68 dba |
Rated Output Frequency | 50 Hz/60 Hz | 50 Hz/ 60 Hz |
Rated Output Voltage | 110V/120V/230V/240V | 110V/120V/230V/240V |
D.C. Output | 12V 8.3A | 12V 8.3A |
A.C. Output | 110V/120V/230V/240V | 110V/120V/230V/240V |
How Many output | 3 | 5 |
Rated Power Output(KVA) | 3 | 5 |
Max.Power Output(KVA) | 3.3 | 5.5 |
Total Length | 600 mm | 700 mm |
Total Width | 450 mm | 480 mm |
Total Height | 500 mm | 600 mm |
Net Weight | 55 kg | 75 kg |
Packing Size(mm) | 650*510*565 mm | 750*570*795 mm |
Large-capacity Air Cleaner | N | N |
Fuel IndiCAT-parts-partsor | Y | Y |
Voltmeter | N | N |
Auto Voltage Adjustor | Y | Y |
Oil Alert System | Y | Y |
Curcuit Breaker without Fuse | Y | Y |
Circuit Protector | Y | Y |
Parallel Connection Box | N | N |
Digital Display Control Panel | N | N |
20" Container( UNIT) | MOQ 150 | MOQ 80 |
40" Container( UNIT) | 320 | 170 |
40' HQ(UNIT) | 400 | 180 |
CertifiCAT-parts-partses | CE,GS,EPA,CARB,CSA | CE,GS,EPA,CARB,CSA |