50Hz Cummins Diesel generator Manual , 6 Cylinder , KTA19-G4

Brand Name:GSKA
Model Number:JP-C440S
Minimum Order Quantity:1 unit
Delivery Time:30 days
Payment Terms:T/T L/C, 30% deposit,70% before delivery
Place of Origin:China
Contact Now

Add to Cart

Verified Supplier
Location: Dongguan Guangdong China
Address: No. 2, Shajiao Sijia Gate, Humen Town, Dongguan City, Guangdong Province, China
Supplier`s last login times: within 48 hours
Product Details Company Profile
Product Details

1, Model: CCEC Cummins KTA19-G4, 4-cycle

2, Standby Power:440KW / 550KVA 50HZ

3, Prime Power: 400KW / 500KVA 50HZ

3, Air Intake System:Turbo, Water/Air cooling

4, Fuel System: PT type fuel pump, EFC

5, Cylinder Arrangement:6 in line

6, Rated RPM:1500rpm

7, Governor Type:Electronic

8, Protection Grade:IP23

9, Connecting Type:3 Phase and 4 Wires, “Y” type connecting


50Hz Cummins Diesel generator Manual , 1500rpm


Standby Power(50Hz) 440KW / 550KVA

Prime Power(50Hz) 400KW / 500KVA


Dimension & Weight


Soundproof Type

Overall Size: 4630(mm)×1660(mm)×2250(mm)

Weight: 5700kg


General Features:


Engine (CCEC Cummins KTA19-G4)

Radiator 40OC max, fans are driven by

belt, with safety guard

24V charge alternator

Alternator: single bearing alternator IP23,

insulation class H/H

Absorber

Dry type air filter, double fuel filter, oil filter,

coolant filter

Main line circuit breaker

Standard control panel

Two12V batteries, rack and cable

Ripple flex exhaust pipe, exhaust siphon,

flange, muffler

User manual


Engine Data


Manufacturer / Model: CCEC Cummins KTA19-G4, 4-cycle

Air Intake System: Turbo, Water/Air cooling

Fuel System: PT type fuel pump, EFC

Cylinder Arrangement: 6 in line

Displacement: 19L

Bore and Stroke: 159*159(mm)

Compression Ratio: 13.9:1

Rated RPM: 1500rpm

Max. Standby Power at Rated RPM: 504KW/675HP

Governor Type: Electronic

Exhaust System

Exhaust Gas Flow: 1604L/s

Exhaust Temperature: 557℃

Max Back Pressure: 10kPa

Air Intake System

Max Intake Restriction: 6.23kPa

Consumption: 579L/s

Air Flow: 9800L/s

Fuel System

100%( Prime Power) Load: 203 g/Kw.h

75%(Prime Power) Load: 207 g/Kw.h

50%(Prime Power) Load:: 216 g/Kw.h

100%( Prime Power) Load: 101.9L/h

Oil System

Total Oil Capacity: 50L

Oil Consumption: ≤4g/kwh

Engine Oil Tank Capacity: 38L

Oil Pressure at Rated RPM: 345-483kPa

Cooling System

Total Coolant Capacity: 106L

Thermostat: 82-93℃

Max Water Temperature: 104℃



Alternator SpecifiCAT-parts-partsion

GENERAL DATA


Compliance with GB755, BS5000, VDE0530, NEMAMG1-22, IED34-1, CSA22.2 and AS1359 standards.


Alternator Data


Number of Phase: 3

Connecting Type: 3 Phase and 4 Wires, “Y” type connecting

Number of Bearing: 1

Power Factor: 0.8

Protection Grade: IP23

Altitude: ≤1000m

Exciter Type: Brushless, self-exciting

Insulation Class, Temperature Rise: H/H

Telephone Influence Factor (TIF): <50

THF: <2%

Voltage Regulation, Steady State: ≤±1%

Alternator Capacity: 500KVA

Alternator Efficiencies: 93.8%

Air Cooling Flow: 1.035m3/s



Generating set data:


Voltage Regulation: ≥±5%

Voltage Regulation, Stead State: ≤±1%

Sudden Voltage Warp (100% Sudden Reduce): ≤+25%

Sudden Voltage Warp (Sudden Increase): ≤-20%

Voltage Stable Time (100% Sudden Reduce): ≤6S

Voltage Stable Time (Sudden Increase) ≤6S

Frequency Regulation, Stead State: ≤5%

Frequency Waving: ≤0.5%

Sudden Frequency Warp (100% Sudden Reduce): ≤+12%

Sudden Frequency Warp (Sudden Increase): ≤-10%

Frequency Recovery Time (100% Sudden Reduce): ≤5S

Frequency Recovery Time (Sudden Increase): ≤5S





Competitive Advantage:


High Performance of loading Easy start
Nice protection User-friendly operation
Low running cost Environmental Long service life


China 50Hz Cummins Diesel generator Manual , 6 Cylinder , KTA19-G4 supplier

50Hz Cummins Diesel generator Manual , 6 Cylinder , KTA19-G4

Inquiry Cart 0