3 Pole MCCB Perkins Diesel Generator , P250HE 250 kva Genset

Brand Name:GSKA
Model Number:JP-P250HE
Minimum Order Quantity:20-30 pieces
Delivery Time:3-5 days on receipt of official sales contract
Payment Terms:L/C,D/P,D/A, Alipay, West Union, TT. Cash,Paypal
Place of Origin:China
Contact Now

Add to Cart

Verified Supplier
Location: Dongguan Guangdong China
Address: No. 2, Shajiao Sijia Gate, Humen Town, Dongguan City, Guangdong Province, China
Supplier`s last login times: within 48 hours
Product Details Company Profile
Product Details

1. Standby power: 200.0 kW

2.Engine Make & Model: Perkins 1306-E87TA300

3.Alternator Model: LL5014H

4.Circuit Breaker Type: 3 Pole MCCB

5.Class: ISO 8528 G2

6.Compression Ratio: 16.9:1

7.Displacement: l (cu.in) 8.7 (530.9)

8.Bore/Stroke: mm (in) 116.6 (4.6)/135.9 (5.4)

9.Moment of Inertia: kg m² (lb. in²) 1.54 (5266)

10.Dimensions(mm*in) : 2960 (116.5)*1003 (39.5)*1718 (67.6)


3 Pole MCCB 250kVA Perkins Diesel Generator , P250HE

Output Ratings

Generating Set Model

* P250HE Prime* Standby*

380-415V, 50 Hz

230.0 kVA 250.0 kVA

184.0 kW 200.0 kW

480V, 60 Hz

245.0 kVA 269.0 kVA

196.0 kW 215.2 kW

  • Refer to ratings definitions on page 4.

Ratings at 0.8 power factor.


Technical Data

Engine Make & Model:

Perkins 1306-E87TA300

Alternator Model:

LL5014H

Base Frame Type:

Heavy Duty FabriCAT-parts-partsed Steel

Circuit Breaker Type:

3 Pole MCCB

Frequency:

50 Hz 60 Hz

Engine Speed: RPM

1500 1800

Fuel Tank Capacity: litres (US gal)

350 (92.5)

Fuel Consumption: P230H l/hr (US gal/hr)

48.7 (12.9) 55.3 (14.6)

Fuel Consumption: P250HE l/hr (US gal/hr)

52.6 (13.9) 61.4 (16.2)

P230H / P250HE


Engine Technical Data


Physical Data


Manufacturer: Perkins

Model: 1306-E87TA300

No. of Cylinders/Alignment: 6 / In Line

Cycle: 4 Stroke

Induction: Turbocharged Air To Air Charge Cooled

Cooling Method: Water Governing

Type: Electronic Governing

Class: ISO 8528 G2

Compression Ratio: 16.9:1

Displacement: l (cu.in) 8.7 (530.9)

Bore/Stroke: mm (in) 116.6 (4.6)/135.9 (5.4)

Moment of Inertia: kg m² (lb. in²) 1.54 (5266)

Engine Electrical System:

-Voltage/Ground: 24/Negative

-Battery Charger Amps: 45

Weight: kg (lb)

- Dry: 671 (1479)

- Wet: 698 (1539)


Air System 50 Hz 60 Hz


Air Filter Type: Replaceable Element Combustion

Air Flow:

m³/min (cfm)

-Standby: 16.9 (597) 23.5 (830)

-Prime: 17.6 (622) 24.0 (848)

Max. Combustion Air Intake

Restriction: kPa (in H2O) 6.2 (24.9) 6.2 (24.9)

Radiator Cooling Air Flow:

m³/min (cfm) 324.0 (11442) 414.0 (14620)

External Restriction to

Cooling Air Flow: Pa (in H2O) 125 (0.5) 125 (0.5)


Cooling System 50 Hz 60 Hz


Cooling System Capacity:

l (US gal) 39.8 (10.5) 39.8 (10.5)

Water Pump Type: Centrifugal

Heat Rejected to Water & Lube Oil: kW (Btu/min)

-Standby: 101.3 (5761) 118.6 (6745)

-Prime: 93.8 (5334) 109.2 (6210)

Heat Radiation to Room:

kW (Btu/min)

-Standby: 58.5 (3327) 66.8 (3799)

Cooling System Capacity:

l (US gal) 39.8 (10.5) 39.8 (10.5)

Water Pump Type: Centrifugal

Heat Rejected to Water & Lube Oil: kW (Btu/min)

-Standby: 101.3 (5761) 118.6 (6745)

-Prime: 93.8 (5334) 109.2 (6210)

Heat Radiation to Room:

kW (Btu/min)

-Standby: 58.5 (3327) 66.8 (3799)


Performance 50 Hz 60 Hz


Engine Speed: RPM 1500 1800

Gross Engine Power: kW (hp)

-Standby: 224.0 (300.0) 242.5 (325.0)

-Prime: 205.5 (276.0) 223.5 (300.0)

BMEP: kPa (psi)

-Standby: 2058.0 (298.5) 1857.0 (269.3)

-Prime: 1888.0 (273.9) 1711.0 (248.2)

Regenerative Power: kW 20.8 28.6


LubriCAT-parts-partsion System


Oil Filter Type: Spin-On, Full Flow

Total Oil Capacity l (US gal): 26.4 (7.0)

Oil Pan l (US gal): 22.7 (6.0)

Oil Type: API CG4 15W-40

Cooling Method: Water


Fuel System:


Fuel Filter Type: Replaceable

Element Recommended Fuel: Class A2 Diesel

Fuel Consumption: l/hr (US gal/hr)


110% 100% 75% 50%

Load Load Load Load

P230H


Exhaust System 50 Hz 60 Hz

Silencer Type: Level 1

Silencer Model & Qty: SD100 (1) Pressure Drop Across

Silencer System: kPa (in Hg) 8.70 (2.569) 8.70 (2.569)

Silencer Noise Reduction

Level: dB 12 10

Max. Allowable Back

Pressure: kPa (in. Hg) 10.7 (3.2) 10.7 (3.2)

Exhaust Gas Flow:m³/min (cfm)

-Standby: 44.5 (1572) 58.1 (2052)

-Prime: 45.9 (1621) 59.2 (2091)

Exhaust Gas Temperature: °C (°F)

m³/min (cfm)

-Standby: 508 (946) 447 (836)

-Prime: 480 (895) 431 (808)

50 Hz 52.6 (13.9) 48.7 (12.9) 37.6 (9.9) 26.8 (7.1)

60 Hz 61.4 (16.2) 55.3 (14.6) 41.1 (10.9) 29.3 (7.7)


P250HE


50 Hz 52.6 (13.9) 40.4 (10.7) 28.6 (7.6)

60 Hz 61.4 (16.2) 45.0 (11.9) 31.5 (8.3)


(based on diesel fuel with a specific gravity of 0.85 and conforming to BS2869, Class A2)

P230H / P250HE


Alternator Performance Data

Data Item

50 Hz 60 Hz

415/240V

400/230V

230/115V

200/115V

380/220V

220/110V

220/127V

480/277V

240/139V

380/220V

220/110V

240/120V

208/120V

230/115V

440/254V

220/127V

Motor Starting Capability* kVA

495

465

425

546

543

362

425

397

468

Short Circuit Capacity** %

300

300

300

300

300

300

300

300

300

Reactances: Per Unit

Xd X'd X''d

2.780


0.130


0.080

3.000


0.140


0.086

3.320


0.160


0.095

2.320


0.110


0.066

2.660


0.130


0.076

4.210


0.200


0.121

3.540


0.170


0.101

3.830


0.180


0.110

3.170


0.150


0.091

Reactances shown are applicable to prime ratings

  • Based on 30% voltage dip. Improved motor starting capability is available with optional Permanent Magnet generator or AREP excitation.

** With optional Permanent Magnet generator or AREP excitation.


Alternator Technical Data


Physical Data Operating Data

Manufacturer: FG WILSON

Overspeed: RPM 2250

Model: LL5014H

Voltage Regulation (steady state) (%): + /- 0.5

No. of Bearings: 1

Wave Form NEMA = TIF:50

Insulation Class: H

Wave Form IEC = THF: 2.0%

Winding Pitch Code: 2/3 - 6

Total Harmonic Content LL/LN: 4.0%

Wires:12

Supression is in line with European Standard

Radio Interference: EN61000-6

Ingress Protection Rating: IP23

Radiant Heat: kW (Btu/min)

-50 Hz: 17.2 (978)

-60 Hz: 18.1 (1029)

Excitation System: SHUNT

AVR Model: R448

P230H / P250HE


Technical Data

3 Phase Ratings and Performance at 50 Hz, 1500 RPM

3 Phase Ratings and Performance at 60 Hz, 1800 RPM


Voltage Prime Model Standby Model Voltage Prime Model Standby Model

P230H P250HE P230H P250HE


kVA kW

kVA kW


kVA kW

kVA kW

415/240V

230.0 184.0

250.0 200.0

480/277V

245.0 196.0

269.0 215.2

400/230V

230.0 184.0

250.0 200.0

220/127V

245.0 196.0

268.0 214.4

380/220V

230.0 184.0

250.0 200.0

380/220V

245.0 196.0

265.0 212.0

230/115V

230.0 184.0

250.0 200.0

240/120V

245.0 196.0

267.0 213.6

220/127V

215.0 172.0

240.0 192.0

230/115V

245.0 196.0

267.0 213.6

220/110V

230.0 184.0

250.0 200.0

440/254V

245.0 196.0

266.0 212.8

200/115V

230.0 184.0

250.0 200.0

220/110V

245.0 196.0

265.0 212.0




208/120V

245.0 196.0

268.0 214.4




230/115V

245.0 196.0

267.0 213.6


Definitions

Standby Rating

These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).



Prime Rating

These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.



Standard Reference Conditions

Note: Standard reference conditions 27°C (80°F) Air Inlet Temp, 152.4m (500ft) A.S.L. 60% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.




Weights and Dimensions


Weights: kg (lb) Dimensions: mm (in)

Net (+ lube oil)

2100 (4630)

Length

2960 (116.5)

Wet (+ lube oil & coolant)

2137 (4711)

Width

1003 (39.5)

Fuel, lube oil & coolant

2432 (5362)

Height

1718 (67.6)


General Data


Documents

A full set of operation and maintenance manuals, circuit wiring diagrams, and commissioning/fault finding instruction leaflets.


Generating Set Standards

The equipment meets the following standards: BS5000, ISO 8528, ISO 3046, IEC 60034, VDE 0530, NEMA MG-1.22.


Warranty

All equipment carries full manufacturer's warranty.


China 3 Pole MCCB Perkins Diesel Generator , P250HE 250 kva Genset supplier

3 Pole MCCB Perkins Diesel Generator , P250HE 250 kva Genset

Inquiry Cart 0