UL listed Motor Thermal Overload Relay / Automatic Magnetic Overload Relay

Brand Name:KRIPAL
Certification:CE, UL
Model Number:UKH-40
Minimum Order Quantity:500 pcs
Delivery Time:20 days and depends on ordering quantity
Payment Terms:T/T, L/C
Contact Now

Add to Cart

Active Member
Address: Daqiao Industrial Zone, Baixiang Town,Yueqing 325603,Zhejiang, China
Supplier`s last login times: within 1 hours
Product Details Company Profile
Product Details

UL listed Motor Thermal Overload Relay / Automatic Magnetic Overload Relay


UKH series thermal overload relays apply to circuit of AC 50Hz or 60Hz, rated voltage to below 660V and rated current . 1A-800A for AC motor overload and open-phase protection during long time or intermittent long time service, which can also protect 3-phase serious imbalance and long starting time of motor or long timer operation, can also be used for corresponding AC contactor for electromagnetic starter.


Applications:


Thermal overload relays are economic electromechanical protection devices for the main circuit.

They offer reliable protection for motors in the event of overload or phase failure.

The thermal overload relay can make up a compact starting solution together with contactors.


Specifications:


Type

Thermal component

Rated current (A)

Range of rated current (A)

UKH-40

UKK-40

5

4.0-6.0

6.5

5.0-8.0

7.5

6.0-9.0

8.5

7.0-10.0

11

9.0-13.0

15

12.0-18.0

19

16.0-22.0

22

18.0-26.0

30

24.0-36.0

34

28.0-40.0


Motion Characteristic:


Three-phase Balance Motion Time

No

Times of the setting current

Motion time

Start condition

Ambient temperature

1

1.05

>2h

Cold state

20±5oC

2

1.2

<2h

Heat state(Following the No.1 test)

3

1.5

<4min

4

7.2

10A

2s< Tp≤10s

≤63A

Cold state

10

4s< Tp≤10s

>63A


Phase-losing Motion Characteristic

No

Times of the setting current

Motion time

Start condition

Ambient temperature

Any two phases

Another phase

1

1.0

0.9

>2h

Cold state

20±5oC

2

1.15

0

<2h

Heat state(Following the No.1 test)


Working Principle of Thermal Relay:


A thermal relay works depending upon the coefficient of expansion of metals. The basic working principle of thermal relay is that, when a bimetallic strip is heated up by a heating coil carrying over current of the system, it bends and makes normally open contacts.


Main benefits:


1. Reliable protection for motors

2. Easy to create starters

3. Optimized match to UKC1 series contactors

4. Single mounting kits and wire reset for remote control available for specific applications.


Main features:


1. Trip class 10

2. Adjustable current setting ranges

3. Overload protection with phase loss sensitivity

4. Temperature compensation up to +60°C

5. Automatic or manual reset, sealable

6. Stop and test function.

China UL listed Motor Thermal Overload Relay / Automatic Magnetic Overload Relay supplier