Add to Cart
1. Main Features and Functions
(1) Display: LED digital meter can display voltage, capacity and time.
(2) Control pattern: keyboard set the whole battery set protective voltage, current, capacity, discharging time.
(3) Automatic stop: It can automatically stop discharging meet following conditions: testing time out, testing capacity out and protective voltage out.
(4) Protection: When high temperature, opposing connection, battery cable disconnection occur, load bank will give alarm sound and automatically cut off the load.
(5) The parameter set in last time could be saved automatically to avoid the same work for the same battery model.
2. Technical Parameters Sheet
DC300-100 DC Automatic load bank
Model | DC300-100 |
Nominal voltage | DC300V |
Discharge voltage | It can discharge during 112V to 375V and 300V±10% guarantee the highest current 100A, can discharge for long time, changing according to Ohm's Law. |
Protection voltage | 1-375V |
Discharge current | 1-100A |
Discharge time | 1minute-99hours59minutes |
Discharge capacity | 1-9999Ah |
Precision | Current 0.1A,Voltage 0.1V |
Constant-current Discharge Control precision | ±(0.3%+0.2A) |
Working power supply | AC single phase 220V±10%,50Hz |
Cooling | Forced air cooling |
Ambient temperature | -10℃ - +40℃ |