MC090S U Microwave Motion Sensor Eight DIP Switch Setting FCC

Brand Name:merrytek
Certification:FCC
Model Number:MC090S U
Minimum Order Quantity:100
Delivery Time:1, Sample and small order: Within 5 working days after receiving your payment. 2, Bulk order: 3-4 weeks after receiving deposit.
Place of Origin:Shenzhen
Contact Now

Add to Cart

Verified Supplier
Location: Shenzhen Guangdong China
Address: 101-1101, Building 17, Dianda Guyuan Industrial Park, Mashantou Community, Matan Street, Guangming District, Shenzhen
Supplier`s last login times: within 33 hours
Product Details Company Profile
Product Details

Microwave Motion Sensor MC090S U, Batch over FCC, 120-277VAC, Superior Immunity to Interference


1. Features


  • Eight DIP switch setting, distance, time, daylight sensor, multi-speed adjustable.

  • Ultra-small mounting size, multiple mounting options, support for top and bottom mounting options.

  • Super cost-effective, support a variety of lamps, tri-proof lamps, ceiling lamps.

  • The infrared sensor is used to filter out the light sensor, and the light sensitivity value is more accurate, and is not affected by cloudy and sunny days.

  • Low impedance 5.8G antenna for superior immunity to interference.

  • Batch over FCC, TUV certification.

2. Parameter


InputOperating Voltage Range120-277VAC 50/60Hz
Rated Voltage120-277VAC 50/60Hz
Stand-by Power≤0.5W
Surge TestBetween L and N: 1KV
OutputWorking ModeON/OFF
Type of LoadResistive or Capacitive
Load Capacity

200W@120VAC, 400@270VAC (Capacitive)

400W@120VAC, 400@270VAC (Resistive)

Current of LoadN/A
Load surge current30A relay - 30A (test twidth 500us @230Vac at 50% Ipeak, cold start at full load) or 60A (test twidth 200us @230Vac at 50% Ipeak, cold start at full load)
SensorOperating Frequency5.8 GHz ±74.9 MHz.ISM wave band
Transmitting power0.5mW Max.
Hold time5S/30S/60S/3min/5min/10min/20min/30min
DIM downN/A
Cut offN/A
Detection Area100% / 75% / 50% / 25%
Daylight Sensor2Lux/10Lux/25Lux/50Lux/Disable

Detecting Radius

(Installed at 3m high )

Normal moving:4-6m

Fast moving:2-3m


Mounting Height2.5-6 m(Suction Top Installation)
Detecting AngleCeiling mount 150°

Operating

Environment

Operating Temperature-20℃…+60℃ Humidity: 85% (non-condensing)
Storage Temperature-40℃…+80℃
Certificate StandardsSafety standardsEN61058-1, EN61058-1-2
EMC standardsEN300440, EN301489-1, EN55015, EN61547, EN61000-3-2, EN61000-3-3, EN62479
Environmental RequirementRoHS
CertificateTUV & FCC
OthersInput/output terminal specifications0.5-0.75mm2
IP RatingIP20
Protection ClassClass II
InstallationBuilt-in installation
Dimension72*36*24.5mm
PackageBubble bag + partition + outer box (K=A)
Net Weight38g
Lifetime5 years warranty @Ta 230V full load

Note

1. “N/A”means not available.

2. Detection area is effected on volume of motion object and motion speed. The detection area is tested by a 165cm height person and walking speed is 0.5m/s.

3. Function


On/OFF Function


4. Dimension (mm)


5.Wiring

*The sensor is designed for connect one load only. Connect more than one loads may damage the sensor.


6.Structure

7. Radiation Pattern


*50%,75%,100% detection sensitivity is workable when installed at 5.5m mounting height. Only 25% sensitivity is not able to detect motion signal.


8. Function Dialing Settings

Detection Area

12
ONON100%
ON-75%
-ON50%
--25%
Hold Time
345
ONONON5S
ONON-30S
ON-ON1min
VONON-3min
IV-ONON5min
IIV-ON-10min
ⅢV--ON20min
IX---30min

Daylight Sensor

678
ONONON2Lux
ONON-10Lux
-ON-25Lux
VON--50Lux
IV---Disable

*When set to Disable gear, the sensor will turn on the light as long as the motion of the object is detected, regardless of whether the illumination is adequate or not.

9. Override Function

Quick switch ON/OFF 3 times within 2sec to override sensor function. Lights will switch on all the time. Power off and on again to recover sensor function.

10. Initialization

After power on, the sensor automatically turns on light at 100% brightness. After 10sec, it turns off the light. During the initialization, the sensor is not able to detect movement.

11. Factory settings

Detection Area: 100%, Hold Time: 5S, Daylight Sensor: Disable

12. Use Caution

1. Be sure to cut off the power supply before installing or adjusting the setting of the dial switch.

2. The microwave cannot pass through the metal, make sure there are no metal above the sensor.

3. It has to be at least 3.5mm away from metal around the microwave antenna. It is not allowed to place antenna and metal on the same horizontal.


China MC090S U Microwave Motion Sensor Eight DIP Switch Setting FCC supplier

MC090S U Microwave Motion Sensor Eight DIP Switch Setting FCC

Inquiry Cart 0