General Specifications | |
Sensing distance | 100…2000mm |
Adjustment range | 100…2000mm |
Unusable area | 0…100mm |
Standard target plate | 100mm×100mm |
Transducer frequency | About 112kHz |
Response delay | About 195ms |
Indicators/Operating means | |
LED blue | Power on |
LED yellow | indication of the switching state Flashing: program function object detected |
LED red | permanently red: Error Red,flashing:program function,object not detected |
Electrical specifications | |
Operating voltage UB | 10…30VDC,ripple10%ss |
Power consumption P0 | ≤900 mW |
Output | |
Output type | 1 analogue output 0…10V |
Resolution | evaluation range [mm]/4000, but ≥ 0.35 mm |
Deviation of the characteristic curve | ≤0.2% of full-scale value |
Repeat accuracy | ≤0.1% of full-scale value |
Load impedance | 0…500 Ohm |
Temperature influence | ≤2% from full-scale value |
Ambient conditions | |
Ambient temperature | -25…70℃ |
Storage temperature | -40…85℃ |
Mechanical specifications | |
Connection | Connector M12x1,4-PIN |
Material Housing | brass,nickel-plated |
Transducer | epoxy resin/hollow glass sphere mixture; Polyurethane foam |
External synchronization
The sensor can be synchronised by the external application of a
square wave voltage. A synchronisation pulse at the
synchronisation
input starts a measuring cycle. The pulse must have a duration
greater than 100 μs. The measuring cycle starts with
the falling edge of a synchronisation pulse. A low level > 1 s
or an open synchronisation input will result in the normal
operation
of the sensor. A high level at the synchronisation input disables
the sensor. Two operating modes are available:
1. Multiple sensors can be controlled by the same synchronisation
signal. The sensors are synchronised.
2. The synchronisation pulses are sent cyclically to individual
sensors. The sensors operate in multiplex mode.
Internal synchronization
The synchronisation connections of up to 5 sensors capable of
internal synchronisation are connected to one another. When
power is applied, these sensors will operate in multiplex mode.
The response delay increases according to the number of sensors to
be synchronised. Synchronisation cannot be performed
during TEACH-IN and vice versa. The sensors must be operated in an
unsynchronised manner to teach the evaluation limits.