Three Core Screened High Voltage Cable Insulation Xlpe 99.99% Copper 26 / 35kv

Brand Name:SHANCABLE
Certification:ISO,CE,IEC,TUV,KEMA
Model Number:YJV-26/35KV 3x95mm2
Minimum Order Quantity:Negotiable
Delivery Time:10 Days
Payment Terms:L/C, T/T
Contact Now

Add to Cart

Verified Supplier
Location: Shanghai Hunan China
Address: No.7577 Hunan Road, Pudong New District. Shanghai China
Supplier`s last login times: within 35 hours
Product Details Company Profile
Product Details

26/35KV Three Core Screened High Voltage XLPE Insulated Cable 3x95SQMM


Construction


CU/XLPE/PVC Electrical Cable


- Round bare Copper core stranded according to IEC 60228
- Inner semi-conductive layer
- Core insulation XLPE
- Outer semi-conductive layer
- Semi-conductive tape
- Copper tape screen
- Filler
- PVC inner sheath

- PP Wrapping
- PVC outer sheath (red or black)


Code name:

YJ: XLPE insulation
V: PVC sheath
32:Steel wire armoring—3 cores
22:Steel tape armoring—3 cores
72: Aluminum wire armoring—1 core
62: Stainless steel tape armoring—1 core
ZR: Flame resistant


Application

Used for power transmission and distribution line with voltage rated at 35kV and below.
High and Medium voltage power cable for static application in ground, within and outside facilities, outdoor, in cable canals, in water, in conditions where cables are not exposed to heavier mechanical stress and tensile strain.


MV(26kv 35kv) Power Cable
Model and Description Uo/U(Um)=3.6/6(7.2), 6/6(7.2), 6/10(12), 8.7/10(12), 8.7/15(17.5), 12/20(24), 18/30(36), 21/35(40.5), 26/35(40.5)kVNo.of CoreConductor cross-section area(mm2)
xlpe insulation1 core 3 core10 16 25 35 70 95 120 150 185 240 300 400 500 630 sq mm
Cu core
YJV, N2XSY;PVC sheathed power cable
YJV22;steel tape armoured,PVC sheathed power cable
YJV32,YJV42;steel wire armoured ,PVC sheathed power cable
Al Core
YJLV, NA2XSY; PVC sheathed power cable
YJLV22;steel tape armoured,PVC sheathed power cable
YJLV32,YJLV42;steel wire armoured ,PVC sheathed power cable

Standard

International: IEC 60502, IEC 60228
China: GB/T 12706
Other standards such as BS, DIN and ICEA upon request


Technical data:

Maximum Conductor Temperature: under normal (90 OC), emergency (130OC) or short circuit no more than 5 s (250℃) conditions.
Min. Ambient Temp. 0 OC, after installation and only when cable is in a fixed position
Min. Bending Radius: 15 x cable O.D for single core
12 x cable O.D for multi core

Test voltage6 / 10 kV[kV]21 / 5 min.
12 / 20 kV[kV]42 / 5 min.
18 / 30 kV[kV]63 / 5 min.
Temperature rangein motion-5°C till +70°C
fixed-20°C till +70°C
Operating temperatureshort circuit°C250
Short circuit timemax.[sec]5
Bending radiusmin.x diameter15
FlammabilitystandardEN 60332-1-2

Nom. Cross-section of conductorStrands No./Dia. Of ConductorInsulation ThicknessInner Sheath ThicknessDia. Of Armor WireSheath ThicknessApprox. O.D.

Approx.

Weight

Max. D.C Resistance of Conductor (20 ℃)Testing Voltage A.CCurrent Rating
mm2pc/mmmmmmmmmm(mm)kg/kmΩ /kmkV/5minIn air (A)In soil(A)
3 × 5010/2.5281.83.153.580.093760.38763175180
3 × 7014/2.5281.83.153.684.0104260.26863220220
3 × 9519/2.5281.83.153.787.0114750.19363255265
3 × 12024/2.5281.83.153.890.0125980.15363290300
3 × 15030/2.5281.83.153.993.0138550.12463330340
3 × 18537/2.5281.83.154.096.0152330.099163435380
3 × 24048/2.5282.03.154.2102.0174810.075463495435
3 × 30061/2.5282.03.154.4107.0197310.060163565485
3 × 40061/2.9782.03.154.6114.0234220.047063640520