Fully Hermetic Scroll Compressor 3 Phase Heat Pump Package Unit 2012×1840mm

Brand Name:EuroKlimat
Certification:ISO9001, ISO14001, OHSAS18001, CRAA, CQC
Model Number:EKAC 220BR1 Basic Model
Minimum Order Quantity:1
Delivery Time:15 working days after received your payment
Payment Terms:L/C, T/T
Contact Now

Add to Cart

Active Member
Location: Dongguan Guangdong China
Address: Euroklimat Industrial Park, Huangjiang Dongguan Guangdong China 523766
Supplier`s last login times: within 2 hours
Product Details Company Profile
Product Details

Eco-friendly Heat Pump Package Unit -Air Cooled Modular Combination 315-504kW


Specifications:


Model EKAC1100BR1EKAC1320BR1EKAC1540BR1EKAC1760BR1
Unit combinationMaster unitEKAC220BR1MEKAC220BR1MEKAC220BR1MEKAC220BR1M
slave unit4*EKAC220BR1S5*EKAC220BR1S6*EKAC220BR1S7*EKAC220BR1S
Nominal cooling capacitykW315378441504
USRT89.6107.52125143
×104kcal/h27.132.523843
Nominal heating capacitykW340408476544
USRT96.7116.04135155
×104kcal/h29.2535.14147
Nominal cooling input powerkW95114133152
Nominal heating input powerkW99118.8138.6158.4
Power supply 380-415V/3Ph/50Hz
RefrigerantType R410A
Control Electronic expansion valve
CompressorType Fully hermetic scroll compressor
Lubricant Grease (POE-160SZ)
Qty.Set10121416
FanType Axia fan with large blade and low noise
Qty.Set10121416
Water side heat
exchanger
Type     
Water flow for
cooling
m3/h5464.875.686.4
Water flow rate
in heating mode

m3/h
58.570.281.993.6
Water pressure dropkPa43434343
Recommended diameter for general inlet/outlet water pipeinch≥4≥5≥5≥6
Power cable specificationSection area of live line
mm2
≥120≥150≥190≥245
Qty. of live lines3
Section area of null line
mm2
≥4
Qty. of null lines1
Section area of grounding line
mm2
≥60≥75≥90≥105
Qty. of grounding lines1
DimensionsL x Hmm2012×1840
Widthmm5860710558607105
Unit weightNet weightkg2575309025753090
Operating weightkg2625315026253150

Note
■ Test conditions for nominal cooling capacity: outlet water temperature 7°C; water flow: 0.172m3/(h·kw); outdoor ambient temperature 35°C.Note:

■ Test conditions for nominal heating capacity: outlet water temperature 45°C; water flow: 0.172m3/(h·kW); outdoor dry/web bulb temperature 7°C/6°C.

■ Water resistance at the air conditioner side includes water pressure drop of the unit and the attached Y strainer.

■ Main Pipes of combined units need to be customized and installed on site. The diameter of the pipes must meet design requirements. EK does not provide the pipes.

■ Modular units can be formed using the 1 - 16 basic modules of same type or of different types as per practical needs. The above table lists the parameters for common module combinations.

■ For on-site electric wiring, see the name plate or installation menu of the unit.


Description


The modular air-cooled heat pump unit with environment friendly refrigerant model uses new-generation R410A refrigerant which does not cause ozone depletion. The unit features optimized system design and an excellent COP. The unit is not only cost effective but also environment friendly,
easy to operate, reliable in performance, and can be installed flexibly. Therefore, units of this series are widely used in dining halls, bars, hotels, offices, top-tier clubs, hospitals, etc.


Features


Environment Friendliness and Excellent Performance


The unit uses environment friendly refrigerant R410A.

• The R410A refrigerant does not cause any ozone depletion.

• The heat exchange performance is excellent, improving the COP.

• Less refrigerant is used, reducing the green house effect.


Efficient and Energy Saving, Greatly Cutting Down Running Cost


The unit features an efficient scroll compressor and heat exchanger. Modules of the system are best matched to improve heat exchange efficiency. The unit uses efficient and environment friendly refrigerant R410A, providing a higher COP. Multi-loop compressors are used to provide multiple capacity adjustment gears. This reduces startup current and electric investment. Excellent COP greatly reduces energy consumption and running cost.


Easy Installation and Simple Maintenance


Before powering on and turning on the unit, you just need to connect the water pipe of each module to the main water pipe. A special access door is provided so that any inter parts of the unit can be conveniently serviced.


The unit is quiet and comfortable during operation


• A low-sound fan generates little operation sound and vibration.

• R410A scroll compressor generates little operation sound and vibration.

• A flexible installation base further reduces operation vibration.

• Air outlet pipes of the compressor are optimized to reduce vibration passed to the unit.

China Fully Hermetic Scroll Compressor 3 Phase Heat Pump Package Unit 2012×1840mm supplier

Fully Hermetic Scroll Compressor 3 Phase Heat Pump Package Unit 2012×1840mm

Inquiry Cart 0