Introduction
Current transformers typically consist of a silicon steel ring core
wound with many turns of copper wire as shown in the illustration
to the right. The conductor carrying the primary current is passed
through the ring. The CT's primary, therefore, consists of a single
'turn'. The primary 'winding' may be a permanent part of the
current transformer, i.e. a heavy copper bar to carry current
through the core. Window-type current transformers (aka zero
sequence current transformers, or ZSCT) are also common, which can
have circuit cables run through the middle of an opening in the
core to provide a single-turn primary winding. To assist accuracy,
the primary conductor should be centered in the aperture.
PARAMETERS
Technical parameters | |
Standards | IEC60044; IEC 61869; ANSI/IEEE C57.13 |
Rated primary current | 50-600A |
Rated load | ≤30VA |
Rated frequency | 50Hz or 60Hz |
Rated secondary current | 5A or 1A |
Rated short-time thermal current | 40kA, 1S |
Rated dynamic current | 63kA |
Rated insulation level | 12/42/75KV |
FS | ≤10 |
Mechanical parameters | |
Material | Epoxy resin |
Weight (kg) | 18 |
Operating conditions | |
Operating temperature | -10°C to +55°C |
Daily average temp | <+40°C |
Storage temperature | -40°C to +70°C |
Altitude | <1000 meters |
Condition | No existence of severely begrimed, erosive and radioactive gas in the air. Permission of long-term operation under rated current. |
Technical data
Rated Current Ratio | Accuracy Class | Rated Output(VA) |
50/1 | 10P5 | 2 |
60/1 | 2 | |
75/1 | 2 | |
100/1 | 2 | |
150/1 | 10P10 | 2.5 |
200-300/1 | 2.5 | |
400-600/1 | 2.5 | |
50/5 | 10P5 | 5 |
75/5 | ||
100/5 | 5 | |
150-300/5 | 10P10 | 5 |
350-600/5 | 10 |
Overall Dimensions