Current Injection CT PT Analyzer 1200A , Circuit Breaker Tester Light Weight

Brand Name:GFUVE
Certification:CE ISO
Model Number:TEST-902
Minimum Order Quantity:1 Set
Payment Terms:Western Union, T/T, L/C, MoneyGram
Place of Origin:CHINA
Contact Now

Add to Cart

Verified Supplier
Location: Beijing Beijing China
Address: Oriental HuaRui A, No. 150 Guanzhuang Road, Chaoyang District, Beijing, 100024, China
Supplier`s last login times: within 37 hours
Product Details Company Profile
Product Details

2200A large Primary Current injection CT PT Analyzer for testing using

TEST-902 primary current injection test set adopts ARM chip to control the output process and large capacity of toroidal transformer. It is equipped with LCD screen display current meter, also showed primary current value, secondary current value, turn ratio and the action time. Aluminum alloy body with PC panel component the shell.TEST-902 is mainly applied to test CT turn ratio in the power system and the contact resistance etc, which need large current.

High-current generator is a necessary equipment in all walks of life in electrical commissioning needs


large current place, used in power plants, substations, electrical manufacturers and scientific research,


laboratory and other units, belonging to short-term or intermittent working system, It has a small size, light


weight, good performance, easy to use and maintenance features.

PARAMETERS

Electrical parameters 
Accuracy±0.5%
Power Supply (AC)220V±10%·50A, 50Hz/60Hz or
110V±10%·100A, 50Hz/60Hz
Current Output (AC)2000A·6V or 1000A·12V
Capacity12KVA
The current output waveform distortion≤5%
Primary current 
Range0-2200A
Resolution0.1A
Accuracy<0.5%
Secondary measurement 
Range0-6A
Resolution0.001A
Accuracy<0.5%
Current duration 
2000A range2000A 2-3minutes
1000A 3-6minutes
1000A range1000A 2-3minutes
With timer
Range0.0001~999.99S
Resolution0.001S
Accuracy<0.5%±5 words
Mechanical parameters 
Dimensions (W×D×H) (mm)360×300×295and320×300×300
Weight (kg)Control Host 35kg,
External voltage regulator weight 15kg
Environmental conditions 
Temperature-10°C to 40°C
Relative humidity≤80%

SELECTION GUIDE

ModelACCU
RACY
Primary
current
AMMETER
(0-6A)
TIMERPOWERINJECTION CURRENT TIMEDIMENSION(W×D×H)(mm)WEIGHTREMARK
TEST-9010.5%0-1100AYESYES5KVA1000A: 2-3min;
500A:3-6min
430×260×26025KGIntegrated structure
TEST-9020.5%0-2200AYESOPTIONAL12KVA2000A:2-3min;
1000A:3-6min
360×300×295 and 320×300×30035KG+15KGFission structure
TEST-9030.5%0-3300AYESOPTIONAL15KVA3000A:2-3min;
1500A:3-6min
380×350×360 and 340×290×42048KG+42KGFission structure
TEST-9050.5%0-5500AYESOPTIONAL25KVA5000A:2-3min;
2500A:3-6min
430×430×445 and 550×450×60068KG+55KGFission structure

China Current Injection CT PT Analyzer 1200A , Circuit Breaker Tester Light  Weight supplier

Current Injection CT PT Analyzer 1200A , Circuit Breaker Tester Light Weight

Inquiry Cart 0