GF3031 Three Phase Portable Power Source for voltage up to 500 V

and current up to 120 A


(Accuracy 0.05% or 0.1%)

The GF3031 is a powerful and portable three phase current and voltage source. All test values are generated absolutely synthetically with a high degree of accuracy and stability. The source is available in 12 A, 24A or 120 A.

The GF3031 three phase portable power source is a lightweight and portable current and voltage source based on newest technology and serves for solving this problem by simulating the required load conditions. Operation is performed by integrated 7“ touch screen or via keyboards.

Features

Accuracy class 0.05 or 0.1

Three phase current generation up to 120 A (AC)

Three phase voltage generation up to 500 V

All test values are generated synthetically

7 inch TFT touch LCD

With USB or RS232

Weight light 15Kg

Overload, short circuit, open circuit protection


Functions

Individual load point settings

Programmable phase shift control from 0-360°

Programmable wave form generation for voltage and current

Generation of up to the 51th harmonic in voltage and current

Programmable power factors

Programmable frequency 40-70Hz

Configuration of balanced and unbalanced load points

Color display with graphical interface

Indication of load values, vector diagram and waveform

Current, voltage and phase shift are adjustable to high accuracy individual per phase

User friendly menu guided operation

Operation without need of an external PC.


Electrical parameters 
Accuracy class0.05%, 0.1%
Power supplySingle phase AC 100-265 V, frequency 50/60 Hz
AC Voltage output 
Range (U1, U2, U3 phase)57.7V, 100V, 220V, 380V(Max 500V); range switch automatically
Adjust fineness0.01% RG
Accuracy0.05% RG
Stability<0.01% RG/120s
Distortion degree<0.3% (not capacitive load)
Output power30VA
Full load regulation rate0.01% RG
Full load regulation timeLess than 1mS
Long-term stability± 60 PPM/year
AC Current output 
Range (I1, I2, I3 phase)0.2A, 1A, 5A, 20A, 100A(Max 120A); range switch automatically
Adjustment range(0-120)%RG
Adjust fineness0.01% RG
Accuracy0.05% RG
Stability<0.01% RG/120s
Distortion degree<0.3% (not capacitive load)
Output power20VA(20A), 50VA(100A)
Full load regulation rate0.01% RG
Full load regulation timeLess than 1mS
Long-term stability± 60 PPM/year
Power output 
Accuracy0.05% RG
Stability0.01% RG/120s
Phase angle 
Adjusting range0°-359.99°
Resolution0.001°
Accuracy0.03°
Power factor 
Adjusting range-1 ~ 0 ~ +1
Resolution0.0001
Accuracy0.0005
Frequency 
Adjusting range40-70 Hz
Resolution0.001 Hz
Accuracy0.005 Hz
Temperature drift± 0.5 PPM/°C
Long-term stability± 4 PPM/year
Voltage /Current/Harmonic Setting 
Harmonic number2-51times
Harmonic content0-40%
Harmonic phase0-359.99
Harmonic setting accuracy(10%±0.1%)RD(2)
Mechanical parameters 
Dimensions (W×D×H) (mm)495x390x195
Weight (kg)15
Environmental conditions 
Working temperature0°C to 50°C
Storage condition-30°C to -60°C
Relative humidity≤ 85%

China Portable Secondary Current Injection Test Set , Secondary Injection Test Equipment 300V for relay pretection supplier