TEST-200 200A PRIMARY CURRENT INJECTION TEST SET FOR CURRENT TRANSFORMER ratio test
200A PRIMARY CURRENT INJECTION TEST SET FOR CURRENT TRANSFORMER
TEST-200 200A primary current injection test set adopts ARM Chip to control its output process and large capacity of toroidal transformers. It is equipped with LCD display and current meter; it can show primary current value, second current value, turn ratio and the action time. Packing is used as aluminum alloy body with PC panel. TEST-200 is mainly applied to CT turn ratio testing in the power system and contact resistance test which need large current.
The primary current injection method is usually the preferred test method because it includes the current sensors, wiring, and the current conduction path in the circuit breaker with the test. However, this method has one disadvantage in that it will not always detect sensor wiring and polarity problems.
If performing three-phase primary injection is not feasible, the
sensors and wiring of the circuit breaker should be tested
separately to verify that they are working correctly. The proper
functioning of the trip unit can be tested using primary current
injection, one phase at a time. Two adjacent phases may also be
connected in series and tested as three pairs to check for current
sensor polarity issues.
Because primary current injection testing is a relatively expensive
service, it's usually performed only during the commissioning
(start-up) process to supplement a program of periodic
secondary-current testing. Circuit breakers that are part of a
critical process or engineered safety system are often maintenance
tested using primary injection due to their high reliability
requirements.
Primary current injection test set for low voltage power circuit
breakers
Electrical parameters | |
---|---|
Accuracy | ±0.5% |
Power Supply(AC) | 220V±10%·5A, 50Hz/60Hz or 110V±10%·10A, 50Hz/60Hz |
Current Output (AC) | 200A·5V or 100A·10V |
Capacity | 1KVA |
The current output waveform distortion | ≤5% |
Dual protection | overload electronic protection and software protection |
Primary current | |
Range | 0-240A |
Resolution | 0.1A |
Accuracy | <0.5% |
Secondary measurement | |
Range | 0-6A |
Resolution | 0.001A |
Accuracy | <0.5% |
Current duration | |
200A range | 200A 2-3minutes 100A 3-6minutes |
100A range | 100A 2-3minutes |
With timer | |
Range | 0.0001~999.99S |
Resolution | 0.001S |
Accuracy | <0.5%±5 words |
Mechanical parameters | |
Dimensions (W×D×H) (mm) | 430×260×260 |
Weight(kg) | 20 |
Environmental conditions | |
Temperature | -10°C to 40°C |
Relative humidity | ≤80% |
Model | ACCU RACY | Primary current | AMMETER (0-6A) | TIMER | POWER | INJECTION CURRENT TIME | DIMENSION(W×D×H)(mm) | WEIGHT | REMARK |
---|---|---|---|---|---|---|---|---|---|
TEST-901 | 0.5% | 0-1100A | YES | YES | 5KVA | 1000A: 2-3min; 500A:3-6min | 430×260×260 | 25KG | Integrated structure |
TEST-902 | 0.5% | 0-2200A | YES | OPTIONAL | 12KVA | 2000A:2-3min; 1000A:3-6min | 360×300×295 and 320×300×300 | 35KG+15KG | Fission structure |
TEST-903 | 0.5% | 0-3300A | YES | OPTIONAL | 15KVA | 3000A:2-3min; 1500A:3-6min | 380×350×360 and 340×290×420 | 48KG+42KG | Fission structure |
TEST-905 | 0.5% | 0-5500A | YES | OPTIONAL | 25KVA | 5000A:2-3min; 2500A:3-6min | 430×430×445 and 550×450×600 | 68KG+55KG | Fission structure |
TEST-200 | 0.5% | 0-240A | YES | YES | 1KVA | 200A: 2-3min; 100A:3-6min | 430×260×260 | 20KG | Integrated structure |