11.5kv Vehicle Borne Mobile Packaged Electrical Transformer Station

Brand Name:Tianan Electric
Certification:IEC,,IEEE
Model Number:CBT1-132
Minimum Order Quantity:1 unit
Delivery Time:45 days
Payment Terms:T/T, L/C, D/A, D/P, Western Union
Contact Now

Add to Cart

Verified Supplier
Location: Ningbo Zhejiang China
Address: 3/F, Building B7 , 999 Yangfan Road,High-tech Zone, Ningbo, China 315040
Supplier`s last login times: within 25 hours
Product Details Company Profile
Product Details

110 - 132 KV Power Transformer Vehicle - borne Mobile Prefabricated Substation


General:

Series 110KV Three-phase Two-winding Off-circuit Tap-Changing Power Transformer has all the functions that an ordinary substation has and the service condition is presently good. After the launch of the products, they have Won

good praises from customers for their convenient and high-efficient

superior properties.

Technical parameters:

1. Technical parameters of switch equipment on LV side

No.ItemUnitParameter
1System voltagekV11.5
2Rated voltagekV12
3Rated frequencyHz50
4Rated currentA2000,1600,1250,
5Rated 1min power frequency withstand voltagekV42/48
6Rated lightning impulse withstand voltagekV75/85
7Rated short time withstand currentkA40,31.5,25
8Rated short time withstand times4
9Rated peak withstand currentkA100,80,63
10Rated short circuit breaking currentkA40,31.5,25
11Rated short circuit making currentkA100,80,63
12Rated operation sequenceO 0.3s CO 180s CO
13Mechanical enduranceTimes≥10000
  • Sound level of the substation:≤65 dB
  • Protection grade of enclosure of switch chamber:IP23(when the door for natural ventilation is open); IP43(when the door for natural ventilation is closed).

2. Technical parameters of HV side switch equipment

2.1 Rated technical parameters of disconnector (Table 1)


Table 1

No.ItemUnitParameter
1System voltagekV132
2Rated voltagekV145
3Rated frequencyHz50
4Rated currentA2000 ,1600
5Rated 1min power frequency withstand voltagekV275
6Rated lightning impulse withstand voltagekV650
7Rated short time withstand currentKA25,31.5,40
8Rated short time withstand times3
9Rated peak withstand currentkA63,80,100

2.2 Rated technical parameter of circuit breaker (Table 2)

Table 2

No.ItemUnitParameter
1System voltagekV132
2Rated voltagekV145
3Rated frequencyHz50
4Rated currentA2000
5Rated 1min power frequency withstand voltagekV275
6Rated lightning impulse withstand voltagekV650
7Rated short time withstand current / timeKA/s40/4
8Rated peak withstand currentkA100
9Rated short circuit breaking currentkA40
10Rated short circuit making currentkA100
11DC component%40
12Rated operation sequenceO 0.3s CO 180s CO
13Opening timems35±5
14Closing timems105±15
15Breaking timems≤60
16Non-simultaneity between polesClosingms≤5
Openingms≤3
17Fracture no. of each pole1
18Mechanical enduranceTimes≥6000
19Full capacity continuous breaking timesTimes≥20
20

SF6 gas pressure

(20℃)

Rated valueMPa0.60
Alarm valueMPa0.55
Locking valueMPa0.50
21

SF6 gas moisture

content(μl/l)

Acceptance valuePPm≤150
Operation allowable valuePPm≤300
22SF6 yearly gas leakage rate%≤0.5
23Total weight of each circuit breakerkg2000

2.3 Parameters of current transformer (Table 3, table 4)

Table 3

Rated primary current150,300,500,750,1000,1500,2000
Rated secondary current5A

Rated output capacity and accuracy level


See table 4

Table 4

Current ratioRated output capacity VAMeasure accuracy levelProtection accuracy level

150/5

300/5

500/5

750/5

1000/5

1500/5

2000/5

20

20

30

30,40

40,50

50

50

0.5

0.5

0.5

0.5

0.5

0.5

0.5

5P20

5P20

5P20

5P20

5P20

5P20

5P20

Note: (1) Straight-through type bushing current transformer is attached in the circuit breaker.


China 11.5kv Vehicle Borne Mobile Packaged  Electrical Transformer Station supplier

11.5kv Vehicle Borne Mobile Packaged Electrical Transformer Station

Inquiry Cart 0