Add to Cart
3 Metre Cube Smoke Density Apparatus is used formeasuring the
emission when the cable or optical cable is placed horizontally
underthedefinite firecondition. The equipment comprises a cubic
enclosure and a photometric system.
The specified standard fire source (ethanol 90±1%, methanol 4±1%
and distilled water 6±1%) 1L±0.01L is burned.
IEC 61034 - 1 & 2 Measurement of Smoke density of cables
burning under defined condition
BS 6853 Code of practice for fire precautions in design and
construction of passenger carrying trains
1.Chamber internal size is 3,000mm(W) × 3,000mm(D) × 3,000mm(H).
2.Its configured with a door with test glass windows and in both
faces of the opposite side theres a sealed transparent window
(minimum 100mmX100mm) .
3.Support system to allow separate fitting of Light Source and
Photocell in the outer wall.
4.The Light Source is Dedolight Classic Series Tungsten with 100W.
5.The Dedolight Tungsten power supply is 12V DC.
6.Velocity of light : 2000 lm~3000 lm, and color temperature :
2800K~3200K.
7.The Receptor Photocell is silicone type and has a spectrum
reaction conform to Photopic Observer (similar to a human eye) of
the International Commission on Illumination (CIE).
8.Supplied with customised extraction facilities and all
instrumentation, fans, stands and sample mounting frames.
9.Software shows testing results including the inner chamber
temperature, light transmition etc.
1. Smoke density box test box part:
a. The internal dimensions of the box is 3000mm X 3000mm X 3000mm,
the total internal volume is 27 cubic meters;
b. The inside of the box is made of SUS 304 stainless steel and the
outside is made of iron spray. Due to the burning test process,
corrosive gas is continuously released. The inner wall of the box
is treated with Teflon dark color, which is not only resistant to
corrosive gases. Erosion, while testing, will not cause failure of
test results due to reflective;
c. The test box is equipped with a laboratory door and an
observation window, so that the user can observe the state in the
combustion chamber;
d. On the left and right sides of the wall, a transparent glass
plate is installed, and the light source and the optical receiving
device can be respectively installed on both sides;
e. Open several ventilation holes near the ground to ensure the
balance of atmospheric pressure inside and outside the box.
2. Smoke density test box measurement and data acquisition part:
a. Prepare a desktop fan to evenly agitate the smoke in the
combustion chamber;
b. The top of the box is equipped with a centrifugal fan to
eliminate the smoke generated by the test;c. Surface ignition
device, remote ignition to ensure the safety of test personnel;
d. In the preparation of combustion test brackets and stainless
steel alcohol trays;
e. The light source is an imported light source, and the test light
source is controlled by a constant current source, and has higher
stability;
f. The light source is accepted as a silicon photocell, equipped
with a cosine calibration device and a color filter. Through this
measure, a higher human eye matching degree can be achieved;
g. Standard transmittance, using 19 cabinet floor installation,
built-in touch screen computer and printer.
3. Smoke density test box optical technical parameters:
a. Using a constant current source to control the light source, the
data is more stable and reliable than the constant voltage mode;
b. Can automatically obtain the optical gear position, the general
accuracy is 0.01%;
c. Matching error: f1 ≤ 4%, the overall linear accuracy is 1%.
27 cubic meters wire and cable smoke density test box, developed according to IEC 61034, BS 6853, GB/T17651.1~2 test standards, mainly used for wire and cable and optical cable smoke density performance testing. During the test, when the smoke is generated, the light path is blocked by the smoke, and the optical transmittance is continuously changed, thereby obtaining the minimum transmittance value and the test time for achieving the minimum transmittance.
Standards:
BS:BS 6853
IEC:IEC 61034-1&2: 2005
Dimension:3150 mm (W) x 3150 mm (D) x 3150 mm (H)
Weight:240kg
Installation requirements
Electrical: 110V AC 60Hz / 230V AC 50Hz
Ambient Temperature: Operating 10°C to 35°C
3 Metre Cube Smoke Density Test Apparatus.pdf
How are fire protection products tested?
Many fire tests are run by official laboratories for the purpose of
product certification. However, some manufacturers of fire
protection products also maintain their own facilities and run
tests for R & D purposes before going to the expense and
exposure of a test at a third party facility.