Dry Type High Pressure Shell And Tube Heat Exchanger For Rooftop HVAC Units

Brand Name:GREEFOUN
Certification:CE
Model Number:QXU260S14
Minimum Order Quantity:1piece
Delivery Time:within 15days
Payment Terms:T/T, L/C, Western Union
Contact Now

Add to Cart

Active Member
Location: Wuhan Hubei China
Address: No.18, Yinhu Development Zone, Dongxihu District Wuhan China
Supplier`s last login times: within 24 hours
Product Details Company Profile
Product Details

U - Shaped Dry Type


Tube Heat Exchanger for Rooftop HVAC Units


Dry Type High Pressure Shell And Tube Heat Exchanger For Rooftop HVAC Units from the shell, heat


pipe bundle, tube plate, baffle (baffle) and the composition of the box and other components. The shell is


mostly cylindrical, with tube bundles inside, tube ends fixed on the tube plate. Heat and heat of the two


kinds of fluid, one in the tube flow, known as the pipeline fluid; another flow outside the tube, known as the


shell process fluid. In order to improve the heat transfer coefficient of the fluid outside the tube, a number


of baffles are usually installed in the housing. The baffle can increase the shell-side fluid velocity, forcing


the fluid to pass through the tube bundle several times according to the specified path, and enhance the


turbulence of the fluid. The heat transfer tubes may be arranged in equilateral triangles or squares on the


tubesheet. The equilateral triangular arrangement is more compact, the turbulence of the tube is high,


and the heat transfer coefficient is large. The square arrangement is convenient for cleaning outside the


tube and is suitable for the fluid which is easy to scale.


The fluid is once referred to as a pipe by pipe bundle once; every time the shell is once referred to as a


shell side. Illustrated as the simplest single-shell single-tube heat exchanger, referred to as 1-1 heat


exchanger. In order to improve the fluid velocity in the pipe, a partition plate can be provided at both ends


of the pipe box, and all the pipes are divided into several groups. So that each time the fluid only through


the part of the tube, and thus in the tube bundle back and forth many times, which is called multi-tube.


Similarly, in order to improve the flow rate outside the tube can also be installed in the shell longitudinal


baffle, forcing the fluid through the shell space several times, known as the multi-shell process. Multi-tube


and multi-shell can be used in conjunction with the application.


U SHAPED TUBE DRY EVAPORATOR (SINGLE CIRCUIT)


CAPACITY: 120KW TO 270KW


ModelsQXU120S8QXU135S8QXU155S8QXU185S10QXU220S10QXU270S10

Rated data

Refrigerant R22

ti=12°C te=2°C

tu=7°C Dts=5°C

QnKW120135155185220270
Kcal/h(×103 )103.2116133.3159180232
Wnm3 /h20.323.226.731.837.846.4
Wmm3 /h252830414365
Dpnbar0.410.440.370.360.430.42

ModelsQXU120S8QXU135S8QXU155S8QXU185S10QXU220S10QXU270S10
Dimension(mm)A181521152315232026542654
B219219219273273273
C180180180200234234
D153018302030200022802280
E240240240300300300
VentS11/21/21/21/21/21/2
OutletS21/21/21/21/21/21/2
ConnectionW(DN)808080100100100
D1(mm)353535353535
D2(mm)545467678080
P(kg)145155163232279289

Qn-rated refrigerating capacity Wn-cooling water flow Wm-maximum cooling water flow

Dpn-pressure drop of recirculating cooling water Dts-overheat temperature


U SHAPED TUBE DRY EVAPORATOR (DOUBLE CIRCUIT)


CAPACITY: 120KW TO 310KW


ModelsQXU120D8QXU135D8QXU155D8QXU185D10QXU220D10QXU270D10QXU310D10

Rated data

Refrigerant R22

ti=12°C te=2°C

tu=7°C Dts=5°C

QnKW120135155185220270310
Kcal/h(×103 )103.2116133.3159189232267
Wnm3 /h20.623.226.731.837.846.453.3
Wmm3 /h25283041436568
Dpnbar0.410.440.370.360.430.420.43

ModelsQXU120D8QXU135D8QXU155D8QXU185D10QXU220D10QXU270D10QXU310D10
Dimension(mm)A1815211523152320232026542654
B219219219219273273273
C200200200200234234234
D1530183020302000200022802280
E240240240300300300300
VentS11/21/21/21/21/21/21/2
OutletS21/21/21/21/21/21/21/2
ConnectionW(DN)89898989114114114
D1(mm)22222222353535
D2(mm)42424242545454
P(kg)145155163232255279296

Qn-rated refrigerating capacity Wn-cooling water flow Wm-maximum cooling water flow

Dpn-pressure drop of recirculating cooling water Dts-overheat temperature


CONDENSER SERIES SINGLE CIRCUIT


CAPACITY: 220RT TO 426RT


ModelRefrig. ton (RT)Refrig. ton (104kcal/h)Dimension (mm)Weight (kg)Max. water flow
DT1TACEH1H2
QXC220S16A22078.5542628603326150530260310310730165.8
QXC240S16A24081.6542628603326150530260310310763181
QXC260S20A26084.3648032003666150530280310310802195.5
QXC280S20A28088.2448032003666150530280400290841211
QXC320S20A32095.2148032003666150600280400290912240.6
QXC340S22A34098.6853035003966150600300400290963256
QXC380S22A380106.53530350039661506503004002901015285.5
QXC426S22A426115.62530380042661506503004002901088320

ModelS (Vent)

P (fluoride inlet)

Copper pipe diameter (inch)

L(fluoride outlet)

Copper pipe diameter (inch)

W (standard port)W (optional port)
FPT(inner pipe thread)Male flangeMale flange
QXC220S16A3/83-1/81-5/8DN125DN125
QXC240S16A3/83-1/81-5/8DN125DN125
QXC260S20A3/83-1/81-5/8DN125DN125
QXC280S20A3/84-1/82-1/8DN150DN150
QXC320S20A3/84-1/82-1/8DN150DN150
QXC340S22A3/84-1/82-1/8DN150DN200
QXC380S22A3/84-1/82-5/8DN200DN250
QXC426S22A3/84-1/82-5/8DN200DN250

COOPERATED CLENTS

China Dry Type High Pressure Shell And Tube Heat Exchanger For Rooftop HVAC Units supplier

Dry Type High Pressure Shell And Tube Heat Exchanger For Rooftop HVAC Units

Inquiry Cart 0