Add to Cart
15kv 150mm2 xlpe underground steel wire armored power cables single
core or three phase
Detailed Product Description
Note:
Insulation identification as per standards or customer requirement
Applications
Laying in room ,tunnel ,cable trench ,and pipes.
Standards
International: IEC 60502, IEC 60228, IEC 60332, IEC 60754
China: GB∕T 12706.2-2008, GB∕T 19666-2005
Other standards such as BS,VDE and ICEA upon request
Certificates
CE, SGS, KEMA and more others at request
What is LSOH Power Cable
Typical structure of LSOH flame-retardant cable: non-metallic cable
cladding material is LSOH flame-retardant material with different
properties. This structure enables the cable to pass class A tests
in IEC 60332-3-22 and related tests in IEC 60754 and IEC 61034.
Benefits of FR Cable
When a fire occurs, the combustion of combustibles in the ordinary
power system will produce a large amount of halogen-containing
smoke. The LSOH power cable and the LSOH building materials used
together can effectively reduce the total amount of smoke released
by combustible combustion and the content of halogen, so as to
reduce the casualty rate in the fire.
The cable has better axial tension resistance.
Constructions
Conductor : Compact stranded copper conductor, Cl.2 as per IEC
60228
Conductor Screen: Semi-conductor
Insulation : XLPE(cross-linked polyethylene) rated at 90 ℃
Insulation Screen: Semi-conductor
Screen : Copper tape
Interlining: LSOH Flame Retardant Polyolefin, black
Armouring: SWA(Steel Wire Armouring)
Sheath : LSOH Flame Retardant Polyolefin, black
Technical data
Rated voltage: 8.7/10 kV
Maximum Conductor Temperature: under normal (90 ℃), emergency
(130℃) or short circuit no more than 5 s (250℃) conditions.
Min. Ambient Temp.: The cable shall be pre heated if the ambient
temperature is below 0℃
Min. Bending Radius: single core cable 20(d+D)±5%
Multi-core cable 15(d+D)±5%
Technical Specifications
Nom. Cross-section of conductor | Strands No./Dia. Of Conductor | Insulation Thickness | Thickness of Copper Strip | Diameter of steel wire | Sheath Thickness | Approx. O.D. | Approx. | Max. D.C Resistance of Conductor (20 ℃) | Testing Voltage A.C | Current Rating | |
Weight | In air (A) | In soil(A) | |||||||||
1×25 | 7/2.17+0.01 | 4.5 | 0.12 | 1.60 | 1.8 | 28.1 | 1102 | 0.727 | 35 | 165 | 160 |
1×35 | 7/2.56+0.01 | 4.5 | 0.12 | 1.60 | 1.9 | 29.3 | 1245 | 0.524 | 35 | 205 | 190 |
1×50 | 19/1.86+0.01 | 4.5 | 0.12 | 1.60 | 1.9 | 30.6 | 1422 | 0.387 | 35 | 245 | 225 |
1×70 | 14/2.56+0.01 | 4.5 | 0.12 | 1.60 | 2.0 | 32.5 | 1701 | 0.268 | 35 | 305 | 275 |
1×95 | 19/2.56+0.02 | 4.5 | 0.12 | 2.00 | 2.1 | 35.1 | 2107 | 0.193 | 35 | 370 | 330 |
1×120 | 24/2.56+0.02 | 4.5 | 0.12 | 2.00 | 2.1 | 36.6 | 2408 | 0.153 | 35 | 430 | 375 |
1×150 | 30/2.56+0.01 | 4.5 | 0.12 | 2.00 | 2.1 | 38.0 | 2723 | 0.124 | 35 | 490 | 425 |
1×185 | 37/2.56+0.02 | 4.5 | 0.12 | 2.00 | 2.2 | 40.0 | 3170 | 0.0991 | 35 | 560 | 480 |
1×240 | 48/2.58+0.02 | 4.5 | 0.12 | 2.00 | 2.3 | 42.4 | 3824 | 0.0754 | 35 | 665 | 555 |
1×300 | 60/2.58+0.02 | 4.5 | 0.12 | 2.00 | 2.3 | 44.6 | 4475 | 0.0601 | 35 | 765 | 630 |
1×400 | 60/2.93+0.02 | 4.5 | 0.12 | 2.50 | 2.5 | 49.5 | 5686 | 0.047 | 35 | 890 | 725 |
1×500 | 60/3.33+0.02 | 4.5 | 0.12 | 2.50 | 2.6 | 53.1 | 8543 | 0.0366 | 35 | 1030 | 825 |
1×630 | 60/3.76+0.02 | 4.5 | 0.12 | 2.50 | 2.7 | 56.7 | 10135 | 0.0283 | 35 | 1200 | 950 |
3×25 | 7/2.17+0.01 | 4.5 | 0.10 | 2.50 | 2.6 | 54.0 | 5028 | 0.727 | 35 | 120 | 125 |
3×35 | 7/2.56+0.01 | 4.5 | 0.10 | 2.50 | 2.7 | 56.4 | 5589 | 0.524 | 35 | 140 | 155 |
3×50 | 19/1.86+0.01 | 4.5 | 0.10 | 2.50 | 2.8 | 60.0 | 6318 | 0.387 | 35 | 165 | 180 |
3×70 | 14/2.56+0.01 | 4.5 | 0.10 | 2.50 | 2.9 | 63.9 | 7374 | 0.268 | 35 | 210 | 220 |
3×95 | 19/2.56+0.02 | 4.5 | 0.10 | 2.50 | 3.1 | 67.9 | 8587 | 0.193 | 35 | 255 | 265 |
3×120 | 24/2.56+0.02 | 4.5 | 0.10 | 2.50 | 3.2 | 71.6 | 9713 | 0.153 | 35 | 290 | 300 |
3×150 | 30/2.56+0.01 | 4.5 | 0.10 | 3.15 | 3.3 | 76.1 | 11693 | 0.124 | 35 | 330 | 340 |
3×185 | 37/2.56+0.02 | 4.5 | 0.10 | 3.15 | 3.4 | 80.4 | 13371 | 0.0991 | 35 | 375 | 380 |
3×240 | 48/2.58+0.02 | 4.5 | 0.10 | 3.15 | 3.6 | 85.7 | 15687 | 0.0754 | 35 | 435 | 435 |
3×300 | 60/2.58+0.02 | 4.5 | 0.10 | 3.15 | 3.8 | 91.0 | 18155 | 0.0601 | 35 | 493 | 485 |
3×400 | 60/2.93+0.02 | 4.5 | 0.10 | 3.15 | 4.0 | 97.9 | 21657 | 0.047 | 35 | 565 | 520 |
Ordering Advice
Rated Voltage
Application Standard: IEC/BS/UL/GB
Number of Cores
Conductor Size & Construction
Type of Insulation
Armored or unarmored. If armor, the armor type & material
The Requirement of Sheath
Length of Cable & Packing Requirement
Other Requirement
PACKING AND SHIPPING
We are capable of meeting the strictest delivery schedules
according to per purchase order. Meeting the deadline is always the
top priority as any delay in the delivery of cable can contribute
to overall project delay and cost overrun.
Cable is supplied in wooden reels, corrugated boxes and coils.
Cable ends are sealed with BOPP self-adhesive tape and
non-hygroscopic sealing caps to protect the cable ends from
moisture. The required marking shall be printed with a
weather-proof material on the outsides of drum according to
customer's requirement.
Product photo