Yanmar 4TNV98 Engine 25kva Genset Diesel Generator LCD display RS485 modem GSM
1. Japan Yanmar 4TNV98 industrial diesel engine
2. Super Silent Low noise canopy
3. Genuine brushless ,avr ,self excited alternator
4. auto and AMF control panels and protection systems
5. ABB Digital auto-start panel
6. Anti Vibration Suspension Absorber
7. Dry type air filter, fuel filter, oil filter
8. 12 hour operation base tank
Alternator
1. World famous brand AC alternator
2. Brushless, 4 poles, rotation magnet
3. IP21-23(NEMA1) enclose is standard for all industrial
alternators
4. H class insulation system
5. AVR self-regulated, voltage regulation rate: ≤±1%
6. Simple installation and maintenance with easy access to
terminals, rotating diodes and coupling bolts
7. Wide range of flange adaptors and single bearing disc coupling
8. Radio interference restraining accords with the stipulation of
VDE0875-N and ISO8528
9. Moisture proof, sand-proof, dustproof, salt-proof and
vibration-proof
Specifications:
Yanmar diesel generator set | ||
GEN-SETS | Model | GNRY25 |
Engine Brand | Yanmar | |
Rated Output(kva) | 25 | |
Power factor(cosφ) | 0.8 | |
Frequency(hz) | 50/60 | |
Fuel Consumption(g/kw.h) | ≤252 | |
The regulating rate of instantaneous voltage | ≤-10%/ +15% | |
The time of steady voltage | ≤1.5sec | |
The waving rate of voltage | ≤0.5% | |
The regulating rate of steady frequency | ≤3% | |
The regulating rate of instantaneous frequency | ≤±5% | |
The time of steady frequency | 3sec | |
The waving rate of frequency | ≤0.25% | |
Diesel engine | Engine model | 4TNV98 |
Cylinder | 4 | |
Rated speed(rpm) | 1500/1800 | |
Cooling method | Closed water cooling | |
Engine type | 4 stroke , direct injection | |
Starting system | Electrical start | |
Alternator | Brand | Stamford/Marathon/ |
Type | Brushless | |
The connecting way of the phase | Three phases four lines | |
Insulation degree | H degree | |
Grading Protection | IP23 |
Controller system
1.Standard control panel, including voltmeter, fequency meter,
ampere meter,water temperature gauge, oil temperature gauge, oil
pressure gauge, AMF control module,oil level indicator, emergency
button,preheating button, battery voltage gauge, hours running
counter for protection and tranfering.
2.It can be with ATS electric control cabinet, including circuit
breaker, LCD or LED auto controller, indicating lamp, transfer
switch,etc.. Automatic transfer switch (ATS) uses update
technology, which can be automatic control for on-off electricity,
remote monitoring, automatic parallel operation