General Specifications

Diaphragm seals are used to prevent process medium form entering directly into the pressure-sensing assembly

of the differential pressure transmitter, they are connected to the transmitter using capillaries filled with fill fluid.

EJA118E Diaphragm Sealed Differential Pressure Transmitters can be used to measure liquid, gas,or steam flow,

as well as liquid level, density, and pressure. EJA118E outputs a 4 to 20 mA DC signal corresponding to the

measured differential pressure.

Its highly accurate and stable sensor can also measure the static pressure which can be shown on the integral

indicator or remotely monitored via BRAIN or HART communications. Other key features include quick response,

remote set-up using communications,and self-diagnostics.

FOUNDATION Fieldbus, PROFIBUS PA and 1 to 5 VDC with HART (Low Power) protocol types are also available.

EJA-E series models in their standard configuration, with the exception of the Fieldbus,PROFIBUS and Low Power

types, are certified as complying with SIL 2 for safety requirement.


STANDARD SPECIFICATIONS

EJA118E Diaphragm Sealed Differential Pressure Transmitter


SPAN AND RANGE LIMITS

Measurement
Span/Range
kPainH2O
(/D1)
mbar
(/D3)
mmH2O
(/D4)
MSpan2.5 to 10010 to 40025 to 1000250 to 10000
Range-100 to 100-400 to 400-1000 to 1000-10000 to 10000
HSpan25 to 500100 to 2000250 to 50000.25 to 5kgf/cm2
Range-500 to 500-2000 to 2000-5000 to 5000-5 to 5kgf/cm2

PERFORMANCE SPECIFICATIONS

Zero-based calibrated span, linear output, wetted parts material code SW for 3-inch flange flush type, fill fluid code B,

and capillary length of 5 m.

For Fieldbus and PROFIBUS communication types, use caribrated range instead of span in the following specifications.

Specification Conformance

EJA-E series ensures specification conformance to at least ±3σ.


Reference Accuracy of Calibrated Span

Includes terminal-based linearity, hysteresis, and repeatability

Measurement spanH
Reference
accuracy
X span±0.2% of Span
X > span±(0.15+0.01 URL/span)% of Span
X100 kPa (400 inH2O)
URL
(upper range limit)
500 kPa (2000 inH2O)

Measurement spanH
Reference
accuracy
X span±0.2% of Span
X > span±(0.15+0.01 URL/span)% of Span
X20 kPa (80 inH2O)
URL
(upper range limit)
100 kPa (400 inH2O)

Square Root Output Accuracy

The square root accuracy is a percent of flow span.


OutputAccuracy
50% or GreaterSame as reference accuracy
50% to Dropout pointReference accuracy × 50
Square root output (%)

Power Supply Effects(Output signal code D and J)

±0.005 % per Volt (from 21.6 to 32 V DC, 350Ω)

Response Time (Differential pressure) “◊”

M and H capsule: 200 ms (approximate value at normal temperature)

When software damping is set to zero and including dead time of 45 ms (nominal)

Static Pressure Signal Range and Accuracy

(For monitoring via communication or on indicator. Includes terminal-based linearity,hysteresis, and repeatability)

Range

Upper Range Value and Lower Range Value of the statice pressure can be set in the range between 0 and Maximum Working Pressure (MWP*). The upper range value must be greater than the lower range value. Minimum setting span is 0.5 MPa (73 psi).

* : Maximum Working Pressure (MWP) is within flange rating pressure.

EJA118E Specification Overview

Refer to the General Specification sheet located under the 'Downloads' tab for detailed specifications.

Measurement Types
Primary VariableDifferential Pressure
Secondary VariableStatic Pressure
Reference Accuracy
Primary Variable±0.04% of Span
±0.025% of Span available
Secondary Variable±0.2% of Span
Response Time
Primary Variable90 msec
Secondary Variable360 msec
Long Term Stability
Primary Variable±0.1% of URL per 10 years
Over-pressure effect
Primary Variable±0.03% of URL
Rangeability
Primary Variable200:1