Add to Cart
Black Leakage Current Sensor Dc Current Sensor _40℃~+85℃ Operating Temperature
TDC-EA series DC leakage current sensor is a kind of new device developed according to principle of electromagnetic induction. Its low current is stable, It is highly insulating between its primary coil and secondary coil, This sensor is used to measure current of signal system, circuit, and leakage monitoring system, as well as to measure current difference.
Electrical data(Ta=25℃±5℃)
Type Parameter | TDC10EA | TDC20EA | TDC30EA | TDC40EA | TDC50EA | Unit |
Rated input (Ipn) | 10 | 20 | 30 | 40 | 50 | mA |
Measure range(Ip) | 20 | 40 | 60 | 80 | 100 | mA |
Turns ratio(Np/Ns) | 1:50 | 1:100 | 1:150 | 1:200 | 1:250 | T |
Rated output | @Ip=±Ipn ±5±1% | V | ||||
Supply voltage | ±12--±15±5% | V | ||||
Consumption current | 20+IpX(Np/Ns) | mA | ||||
Offset voltage | @Ip=0 ≤±50 | mV | ||||
Offset voltage drift | @ -40℃~85℃ ≤±1.5 | mV/℃ | ||||
Linearity | @Ip=0-±Ipn ≤1 | %FS | ||||
Response time | ≤50 | mS | ||||
Galvanic isolation | @ 50HZ,AC,1min 2.5 | KV |
Applications
Variable speed drives
Welding machine
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Electrochemical
Mechanical dimension(for reference only)
Remarks:
1. All dimensions are in mm.
2. General tolerance ±1mm.
Directions for use
When the current will be measured goes through a sensor, the voltage will be measured at the output end.
(Note: The false wiring may result in the damage of the sensor)
The output amplitude of the sensor can be adjusted according to users’ requirements.
Custom design in the different rated input current and the output voltage are available.
Standards
General date
Value | Unit | Symbol | |
Operating temperature | -40 to +85 | ºC | TA |
Storage temperature | -40 to +125 | ºC | TS |
Mass(approx) | 251 | g | M |
Characteristics chart
Characteristic of Output Noise Voltage
Input Current-Output Voltage