Add to Cart
Applications
For laying indoors and outdoors. Able to bear certain traction during installation, but not external mechanical forces. Laying single core cable in magnetic ducts is not allowed.
Construction
Conductor : Copper Conductor as per IEC 60228
≤6mm2 solid (class 1)
>6mm2 stranded (class 2)
≥ 50mm2 Shaped conductoer optional
Insulation : PVC(polyvinyl chloride) rated at 75℃
Sheath : Low smoke zero halogen black or red or customization
Flame retardant: Avaliable as customization
Standards:
Conductor: Compact stranded copper conductor, Cl.2 as per IEC 60228
Mica Tape
Filler
Sheath: LSOH, black or other colors, as per IEC60332,60502-1
Technical data
Nom. Cross-section of conductor | Insulation Thickness | Sheath | Approx. | Approx | Max. D.C. Resistance of Conductor (20°C) | Test Voltage | Current Rating | |
mm2 | mm | Thickness | O.D. | Weight | Ω/km | A.C | ||
mm | mm | kg/km | kV/5min | In air(A) | In soil(A) | |||
4×1.5 | 0.7 | 1.8 | 14.4 | 241 | 12.1 | 3.5 | 20 | 27 |
4×2.5 | 0.7 | 1.8 | 15.4 | 295 | 7.41 | 3.5 | 26 | 35 |
4×4 | 0.7 | 1.8 | 16.5 | 369 | 4.61 | 3.5 | 34 | 45 |
4×6 | 0.7 | 1.8 | 17.8 | 463 | 3.08 | 3.5 | 43 | 57 |
4×10 | 0.7 | 1.8 | 20.9 | 667 | 1.83 | 3.5 | 60 | 77 |
4×16 | 0.7 | 1.8 | 23.4 | 930 | 1.15 | 3.5 | 83 | 105 |
4×25 | 0.9 | 1.8 | 27.1 | 1351 | 0.727 | 3.5 | 105 | 125 |
4×35 | 0.9 | 1.8 | 29.5 | 1772 | 0.524 | 3.5 | 125 | 155 |
4×50 | 1 | 1.9 | 38.4 | 2380 | 0.387 | 3.5 | 160 | 185 |
4×70 | 1.1 | 2 | 43.2 | 3302 | 0.268 | 3.5 | 200 | 225 |
4×95 | 1.1 | 2.2 | 47.3 | 4330 | 0.193 | 3.5 | 245 | 270 |
4×120 | 1.2 | 2.3 | 52.5 | 5374 | 0.153 | 3.5 | 285 | 310 |
4×150 | 1.4 | 2.5 | 58.3 | 6655 | 0.124 | 3.5 | 325 | 345 |
4×185 | 1.6 | 2.7 | 64.7 | 8246 | 0.0991 | 3.5 | 375 | 390 |
4×240 | 1.7 | 2.9 | 73.1 | 10569 | 0.0754 | 3.5 | 440 | 450 |
Product image