Add to Cart
1.05MW high efficiency hot water boiler hot water boiler system for bathing room
High efficiency hot water boiler Superior performance
1. Yongxing Boiler Patented Products
Horizontal internal combustion three-return full wet back design,
100% corrugated furnace, with good thermal expansion, water-cooled
back-combustion chamber, back-fired chamber and rear tube plate
edge-to-side docking, the lowest stress, more reliable quality.
2, large diameter corrugated furnace
The boiler combustion chamber is composed of a large-diameter
full-corrugated furnace, which has a large combustion space,
complete combustion of fuel, effective absorption of heat and
thermal expansion, and large radiation heating surface.
3, sufficient heat
The boiler heating area is designed to be larger than 25 square
meters per ton, fully absorbing effective heat, low exhaust gas
temperature and small heat loss, ensuring sufficient output and
high efficiency.
4, multi-function safety explosion-proof device
The explosion-proof device connected to the furnace is arranged on
the rear plate of the boiler to prevent the high energy of the
venting moment when the fuel is violently detonated in the furnace,
and can be automatically reset. At the same time, it has the
function of viewing the sight glass and the inspection passage, and
is utilized in operation. The adjustment of the combustion flame,
furnace inspection, and easy maintenance.
5, safe precipitation time is enough
The position of the combustion chamber of the boiler is determined.
The water level is determined in accordance with the national
regulations. At the same time, the water level fluctuation time
requirement is strictly in accordance with the international
general norm standards, and there is sufficient safe precipitation
space to ensure the safe operation of the boiler.
6, boiler maintenance is convenient
There is a manhole at the top of the boiler, and a hand hole device
is arranged below the front and rear of the boiler to facilitate
inspection and cleaning of the furnace unit and the bottom of the
boiler.
7, the front and rear smoke box seal is unique
The smoke box adopts double-opening smoke box door, which is
convenient to open, multi-stage labyrinth seal, special sealing
material, good compression performance, complete barrier of smoke
leakage, and can be reused.
8, water temperature, water level protection is reliable
Boiler water temperature, water level setting multiple control
protection, and super smoke temperature protection to ensure the
safety of boiler operation.
9, automatic control level leading
The high efficiency hot water boiler controller adopts Siemens and
Delixi electrical components and has reliable performance. Chinese
and English menu type with LCD display, touch screen type for
remote control of man-machine dialogue.
best hot water boiler systems 0.35MW-14MW Oil Gas Fired hot water
boiler technical datasheet
Main technical parameters of CWNS oil (gas) atmospheric pressure and pressure hot water boiler | |||||||||||||||
Project model | CWNS, WNS series hot water boiler | ||||||||||||||
Rated calorific value (MW) | 0.35 | 0.7 | 1.05 | 1.4 | 2.1 | 2.8 | 3.5 | 4.2 | 5.6 | 7 | 8.4 | 10.5 | 12.6 | 14 | |
Working pressure (MPa) | Normal pressure / pressure | ||||||||||||||
Outlet water temperature (°C) | 85/115 | ||||||||||||||
Backwater temperature (°C) | 60/70 | ||||||||||||||
Boiler thermal efficiency (%) | 91—95 | ||||||||||||||
Feed water temperature (°C) | 20 | ||||||||||||||
Fuel consumption | Diesel (Kg/h) | 32 | 65.4 | 98 | 131 | 196.2 | 261.6 | 327 | 392.4 | 523.2 | 654 | 784.8 | 981 | 1177 | 1310 |
Heavy oil (Kg/h) | 34 | 69.5 | 105 | 139 | 208.5 | 278 | 347.5 | 417 | 556 | 695 | 864 | 1042.5 | 1251 | 1390 | |
Natural gas (m3/h) | 39.5 | 79.3 | 119 | 159 | 237.9 | 317.2 | 396.5 | 475.8 | 644 | 793 | 951.6 | 1189.5 | 1427.4 | 1586 | |
Liquefied gas (m3/h) | 14.2 | 29 | 43.5 | 58 | 87 | 116 | 145 | 174 | 232 | 290 | 348 | 435 | 522 | 580 | |
City gas (m3/h) | 84 | 168.5 | 253 | 337 | 505.5 | 674 | 842.5 | 1011 | 1348 | 1685 | 2022 | 2527.5 | 3033 | 3370 | |
Boiler transportation | Length (mm) | 2800 | 3500 | 4100 | 4500 | 4700 | 4550 | 5700 | 6300 | 7000 | 7200 | 7840 | 8100 | 8230 | 8250 |
Width (mm) | 1600 | 1600 | 1900 | 2000 | 2110 | 2210 | 2500 | 2600 | 2700 | 2800 | 2860 | 3100 | 3100 | 3400 | |
High (mm) | 2000 | 2100 | 2310 | 2360 | 2470 | 2580 | 2800 | 2900 | 3200 | 3300 | 3300 | 3400 | 3400 | 3550 | |
Total power consumption (KW) | 2.3 | 6.7 | 11 | 13.5 | 19 | 21 | 23.5 | 26 | 37 | 37 | 42 | 45 | 52 | 52 | |
Chimney diameter (mm) | 250 | 350 | 430 | 450 | 450 | 550 | 650 | 650 | 650 | 800 | 800 | 900 | 1200 | 1200 | |
Shipping weight (T) | 3.2 | 4.7 | 4.8 | 5.4 | 8 | 9.78 | 13.4 | 15.4 | 17.4 | 17.4 | 23.8 | 30 | 31.6 | 34.5 | |
Heating area (m2) | 3000 | 6000 | 9000 | 12000 | 18000 | 24000 | 30000 | 36000 | 48000 | 60000 | 72000 | 90000 | 108000 | 120000 | |
Water supply capacity (t) | 7 | 15 | 22 | 30 | 45 | 60 | 75 | 90 | 120 | 150 | 180 | 225 | 270 | 300 |