KDI Series Measurement Display Controller With Parameter Password Lock And Power - Off Retention

Brand Name:KACISE
Certification:CE
Model Number:KDI Series
Minimum Order Quantity:1PCS
Delivery Time:5-8 work days
Payment Terms:L/C, D/A, D/P, T/T, Western Union, MoneyGram
Contact Now

Add to Cart

Verified Supplier
Address: i City, No11, TangYan South road, Yanta District, Xi'an,Shaanxi,China.
Supplier`s last login times: within 16 hours
Product Details Company Profile
Product Details

KDI Series Measurement Display Controller with Parameter Password Lock and Power - off Retention


Introduction


KACISE's KDI Series Measurement Display Controller features a parameter password lock and power - off retention. The password lock safeguards the internal parameters from unauthorized changes, ensuring data integrity and stable operation. The power - off retention function ensures that set parameters are saved even when power is off. This is crucial for applications requiring continuous and consistent operation, and with these features, KACISE provides a reliable and secure measurement display controller.


Features


· New concept of computer digital auto-tuning
· Clear and clear measurement display
·· Support multi-machine network communication, communication protocol can be freely set
· Unique full open user-defined interface
· Set parameter power-off permanent retention and parameter password lock
· Fully digital cold junction compensation
· Multi-size external structure size
· AC and DC switching power supply mode


Parameters


Matching with standard indexing temperature sensor:

Input Signal

Indexing

No.

ResolutionSensorRange
B1

Platinum30-platinum6 rhodium


400~1800℃
S1Platinum10-platinum0~1600℃
K1Nickel chromium-nickel silicon0~1300℃
E1

Nickel chromium-constantan


0~1000℃
J1

Iron-constantan


0~1200℃
T0.1

Copper-constantan


-199.9~3200℃
Wre1

Tungsten3-tungsten25


0~2300℃
Pt1001Platinum thermal resistance R0 = 100Ω-199~650℃
Pt1000.1Platinum thermal resistance R0= 100Ω-199.9~320.0℃
Cu500.1Copper thermal resistance R0= 50Ω-50.0~150.0℃

With standard signal transmitter:

Input Signal

Standard Signal

Range

Input ResistanceMatching TransmitterMeasuring Range

various mV signal

0~10mA

4~20mA

0~5V

1~5V

30~350Ω

≥10MΩ

≤250Ω

≤250Ω

≥250KΩ

≥250KΩ

hall transmitter

compatible with DDZ-II type instrument

compatible with DDZ-III type instrument

compatible with DDZ-II type instrument

compatible with DDZ-III type instrument

compatible with remote pressure resistors

set according to user needs.


range:

-1999~9999


Main Technical parameters

Input SignalAnalog

Resistance: standard thermal resistance (remote pressure resistance such as Pt100, Cu50)


Galvanic couples: standard thermocouples ( B, S, K, E, J, T, WRe, etc.)


Current: 0~10mA, 4~20mA, 0~20mA, etc. (Input impedance ≤250Ω)
Voltage: 0~5V, 1~5V, etc.(Input impedance ≥250Ω)

Measuring Range-1999~9999
Accuracy0.2% FS ±1 or 0.5% FS ±1
Resolution1, 0.1, 0.01 or 0.001
Temperature Compensation0~50
Display Method

-19999~9999 measured value display

-19999~9999 set value display

0~100% measured value light column display

LED operating status display

Light Column AccuracyThe light column display accuracy is 1%
Control MethodPosition ON / OFF with backlash
Output Signal

Analog

output


DC 0-5V (load capacity ≤250Ω)

DC 1~5V (load capacity ≤250Ω)

DC 0~10mA (load capacity ≤750Ω)

DC 4~20mA (load capacity ≤500Ω)

Switch

output


Relay control output - Relay ON/OFF with backlash

Contact capacity: AC220V/3A; DC24V/6A (resistive load)


Controllable silicon output-SCR (controllable zero-crossing pulse), can trigger controllable silicon: 400V/100A


Solid state relay output - SSR (solid state relay control signal) output, 6 ~ 24 / 30mA (voltage cannot be adjusted)

Communication

output


Interface mode - Standard serial two-way communication interface: RS-485, RS-232C, RS-422, etc.
Feed outputDC24V, load capacity ≤30mA
control method

Optional 1~4 limit control, LED indication. The control mode is the relay ON/OFF with backlash (user can set it freely)


control accuracy±1
Alarm modeYou can select 1~4 limit alarm, LED indication. The control mode is the relay ON/OFF with backlash (user can set it freely)
Alarm accuracy±1
Temperature compensation0~5 0°C digital temperature automatic compensation
Parameter setting

• Panel touch type press key digital setting

• Parameter setting value is permanently hold when power off

• Parameter setting value Password Lock

Protection method

• Input loop disconnection alarm (when thermocouple or resistance input), relay output, LED indication

• Input over/under range alarm

• Power under voltage automatic reset

•Work abnormally automatic reset (watch dog)

Online communicationThe communication protocol is a two-wire system, a three-wire system or a four-wire system (e.g. RS485, RS232C, RS422, etc. ) can also be specially requested by the user. The baud rate of 300 to 9 6 0 0 b p s can be set freely by the internal parameters of the instrument. The interface and the main unit are separated by photo-electricity, and the communication distance can reach 1.2 km. The system adopts the master-slave communication mode. The whole control loop only needs one two (three, four) core cable, which can realize communication with the host computer. The upper computer can call the device number set by the user, and call the scene of each instrument at any time. Data, and can be used to set internal parameters of the instrument. Equipped with data collector and industrial control software, it can realize online communication between multiple instruments and one or more microcomputers.
Use environment

• Ambient temperature 0~5 0°C

• Relative humidity ≤ 85 R H

• Avoid strong corrosive gases

Power Supply

Normal type :

• A C 220 V + 10 - 1 5 % (50 Hz ± 2Hz linear power source )

Special type:

• A C 90 ~ 260 V- - switch power

• D C 24 V ±2 V- - switch-off power supply

Power consumption

• ≤5 W (A C 220 V linear power supply)

• ≤4 W (A C 90 V~265 V switch power supply)

• ≤4 W (D C 4 V power supply)

Weight420g (AC220V linear power supply)
China KDI Series Measurement Display Controller With Parameter Password Lock And Power - Off Retention supplier

KDI Series Measurement Display Controller With Parameter Password Lock And Power - Off Retention

Inquiry Cart 0