MICROMASTER 430 Types Variable Frequency Drive Inverter 380v Fans Drive
Application
The MICROMASTER 440 inverter is suitable for a variety of variable-speed drive applications. Its flexibility provides for a wide spectrum of applications. These also include cranes and hoisting gear, high-bay warehouses, production machines for food, beverages and tobacco, packaging machines etc.; i.e. applications which require the frequency inverter to have a higher functionality and dynamic response than usual.
The inverter is especially characterized by its customer-oriented performance and ease-of-use. Its large mains voltage range enables it to be used all over the world.
Technical data | MICROMASTER 440 | ||||||||
---|---|---|---|---|---|---|---|---|---|
Mains voltage and power ranges | CT (constant torque) | VT (variable torque) | |||||||
200 V to 240 V 1 AC ±10 % | 0.12 kW to 3 kW | - | |||||||
200 V to 240 V 3 AC ±10 % | 0.12 kW to 45 kW | 5.5 kW to 55 kW | |||||||
380 V to 480 V 3 AC ±10 % | 0.37 kW to 200 kW | 7.5 kW to 250 kW | |||||||
500 V to 600 V 3 AC ±10 % | 0.75 kW to 75 kW | 1.5 kW to 90 kW | |||||||
Input frequency | 47 Hz to 63 Hz | ||||||||
Output frequency | in V/f mode | for inverter 0.12 kW to 75 kW | 0 ... 650 Hz, (limitation to 550 Hz in production to comply with legal requirements) 1) | ||||||
for inverter 90 kW to 200 kW | 0 Hz to 267 Hz | ||||||||
in vector mode | for inverter 0.12 kW to 75 kW | 0 Hz to 200 Hz | |||||||
for inverter 90 kW to 200 kW | 0 Hz to 200 Hz | ||||||||
Power factor | ≥ 0.95 | ||||||||
Inverter efficiency | 0.12 kW to 75 kW: 96 % to 97 %; 90 kW to 200 kW: 97 % to 98 % (Further information is available on the Internet at: | ||||||||
Overload capability CT mode | for inverter 0.12 kW to 75 kW | Overload current 1.5 x rated output current (i.e. 150 % overload capability) for 60 s, cycle time 300 s, and 2 x rated output current (i.e. 200 % overload capability) for 3 s, cycle time 300 s | |||||||
for inverter 90 kW to 200 kW | Overload current 1.36 x rated output current (i.e. 136 % overload capability) for 57 s, cycle time 300 s, and 1.6 x rated output current (i.e. 160 % overload capability) for 3 s, cycle time 300 s | ||||||||
Overload capability VT mode | for inverter 5.5 kW to 90 kW | Overload current 1.4 x rated output current (i.e. 140 % overload capability) for 3 s, and 1.1 x rated output current (i.e. 110 % overload capability) for 60 s, cycle time 300 s | |||||||
for inverter 110 kW to 250 kW | Overload current 1.5 x rated output current (i.e. 150 % overload capability) for 1 s, and 1.1 x rated output current (i.e. 110 % overload capability) for 59 s, cycle time 300 s | ||||||||
Inrush current | not higher than rated input current | ||||||||
Control method | Vector control, torque control, linear V/f characteristic; quadratic V/f characteristic; multipoint characteristic (programmable V/f characteristic); flux current control (FCC) | ||||||||
Pulse frequency | for inverter 0.12 kW to 75 kW | 4 kHz (standard); 16 kHz (standard with 230 V inverters 0.12 kW to
5.5 kW) 2 kHz to 16 kHz (in 2 kHz steps) | |||||||
for inverter 90 kW to 200 kW | 2 kHz (standard with VT mode); 4 kHz (standard with CT mode) 2 kHz to 4 kHz (in 2 kHz steps) |
Output | Rated output current in A for a pulse frequency of | ||||||
---|---|---|---|---|---|---|---|
kW | 4 kHz | 6 kHz | 8 kHz | 10 kHz | 12 kHz | 14 kHz | 16 kHz |
Mains operating voltage 200 V 1/3 AC | |||||||
0.12 to 5.5 | Values correspond to the 4 kHz standard values. No derating, since 16 kHz standard. | ||||||
7.5 | 28.0 | 26.6 | 25.2 | 22.4 | 19.6 | 16.8 | 14.0 |
11 | 42.0 | 37.8 | 33.6 | 29.4 | 25.2 | 21.0 | 16.8 |
15 | 54.0 | 48.6 | 43.2 | 37.8 | 32.4 | 27.0 | 21.6 |
18.5 | 68.0 | 64.6 | 61.2 | 54.4 | 47.6 | 40.8 | 34.0 |
22 | 80.0 | 72.0 | 64.0 | 56.0 | 48.0 | 40.0 | 32.0 |
30 | 104.0 | 91.0 | 78.0 | 70.2 | 62.4 | 57.2 | 52.0 |
37 | 130.0 | 113.8 | 97.5 | 87.8 | 78.0 | 71.5 | 65.0 |
45 | 154.0 | 134.8 | 115.5 | 104.0 | 92.4 | 84.7 | 77.0 |
Mains operating voltage 400 V 3 AC | |||||||
0.37 | 1.3 | 1.3 | 1.3 | 1.3 | 1.3 | 1.2 | 1.0 |
0.55 | 1.7 | 1.7 | 1.7 | 1.6 | 1.5 | 1.4 | 1.2 |
0.75 | 2.2 | 2.2 | 2.2 | 2.0 | 1.8 | 1.5 | 1.3 |
1.1 | 3.1 | 2.9 | 2.8 | 2.5 | 2.2 | 1.9 | 1.6 |
1.5 | 4.1 | 3.7 | 3.3 | 2.9 | 2.5 | 2.1 | 1.6 |
2.2 | 5.9 | 5.6 | 5.3 | 4.7 | 4.1 | 3.5 | 3.0 |
3.0 | 7.7 | 6.9 | 6.2 | 5.4 | 4.6 | 3.9 | 3.1 |
4.0 | 10.2 | 9.2 | 8.2 | 7.1 | 6.1 | 5.1 | 4.1 |
5.5 | 13.2 | 11.9 | 10.6 | 9.2 | 7.9 | 6.6 | 5.3 |
7.5 | 19.0 | 18.1 | 17.1 | 15.2 | 13.3 | 11.4 | 9.5 |
11.0 | 26.0 | 23.4 | 20.8 | 18.2 | 15.6 | 13.0 | 10.4 |
15.0 | 32.0 | 30.4 | 28.8 | 25.6 | 22.4 | 19.2 | 16.0 |
18.5 | 38.0 | 34.2 | 30.4 | 26.6 | 22.8 | 19.0 | 15.2 |
22 | 45.0 | 40.5 | 36.0 | 31.5 | 27.0 | 22.5 | 18.0 |
30 | 62.0 | 58.9 | 55.8 | 49.6 | 43.4 | 37.2 | 31.0 |
37 | 75.0 | 67.5 | 60.0 | 52.5 | 45.0 | 37.5 | 30.0 |
45 | 90.0 | 76.5 | 63.0 | 51.8 | 40.5 | 33.8 | 27.0 |
55 | 110.0 | 93.5 | 77.0 | 63.3 | 49.5 | 41.3 | 33.0 |
75 | 145.0 | 112.4 | 79.8 | 68.9 | 58.0 | 50.8 | 43.5 |
90 | 178.0 | - | - | - | - | - | - |
110 | 205.0 | - | - | - | - | - | - |
132 | 250.0 | - | - | - | - | - | - |
160 | 302.0 | - | - | - | - | - | - |
200 | 370.0 | - | - | - | - | - | - |
Mains operating voltage 500 V 3 AC | |||||||
0.75 | 1.4 | 1.2 | 1.0 | 0.8 | 0.7 | 0.6 | 0.6 |
1.5 | 2.7 | 2.2 | 1.6 | 1.4 | 1.1 | 0.9 | 0.8 |
2.2 | 3.9 | 2.9 | 2.0 | 1.6 | 1.2 | 1.0 | 0.8 |
4.0 | 6.1 | 4.6 | 3.1 | 2.4 | 1.8 | 1.5 | 1.2 |
5.5 | 9.0 | 6.8 | 4.5 | 3.6 | 2.7 | 2.3 | 1.8 |
7.5 | 11.0 | 8.8 | 6.6 | 5.5 | 4.4 | 3.9 | 3.3 |
11.0 | 17.0 | 12.8 | 8.5 | 6.8 | 5.1 | 4.3 | 3.4 |
15.0 | 22.0 | 17.6 | 13.2 | 11.0 | 8.8 | 7.7 | 6.6 |
18.5 | 27.0 | 20.3 | 13.5 | 10.8 | 8.1 | 6.8 | 5.4 |
22 | 32.0 | 24.0 | 16.0 | 12.8 | 9.6 | 8.0 | 6.4 |
30 | 41.0 | 32.8 | 24.6 | 20.5 | 16.4 | 14.4 | 12.3 |
37 | 52.0 | 39.0 | 26.0 | 20.8 | 15.6 | 13.0 | 10.4 |
45 | 62.0 | 52.7 | 43.4 | 40.3 | 37.2 | 32.6 | 27.9 |
55 | 77.0 | 67.4 | 57.8 | 52.0 | 46.2 | 42.4 | 38.5 |
75 | 99.0 | 84.2 | 69.3 | 64.4 | 59.4 | 52.0 | 44.6 |