Product Details

Factory produced Residual Current Earth Leakage Circuit Breaker 63A/30mA 2 Pole 4Pole new type RCCB ELCB


The RCCB is in conformity with the standard of IEC61008.The RCCB can cut off the fault circuit immeditaely on the occasion of shock hazard of earth leakage of truck. Thus it is suitable to avoid the shock hazard and fire caused by earth leakage. The RCCB is mainly suitable for use in varieties of plants and enterprises,building construction 1 phase 230V and 3 phase 400V 50/60HZ.RCCB is not suitable for use on DC pulse system.

Product Description
This series Residual Current Circuit Breaker is applicable to electric circuits with rated voltage 230/400V AC, frequency 50/60Hz and rated current up to 63Amp.

1. Rated sensitivity up to 30mA could be used as supplementary protecting device in case other protecting device fails its protection against electric shock.
2. This series RCCB designed for household installation and other similar application, is for non-professional operation, and no maintenance is required.
3. This series RCCB provides no protection against electric shock resulted from direct contacts of both protected lines,or leakage current between these two lines.
4. Particular devices such as surge protective devices,surge arrester etc are recommended to install at upstream line to RCCB as precaution against potential surge voltage and current occurring at its power input side.
5. Satisfying conditions and applications as mentioned above, RCCB with °∞ON-OFF°± indicating device is considered suitable for isolation function.


Technical Data

1. Provides protection against earth fault/leakage current and function of isolation.

2. High short-circuit current withstand capacity.

3. Applicable to terminal and pin/fork type busbar connection.

4. Equipped with finger protected connection terminals.

5. Automatically disconnect the circuit when earth fault/leakage current occurs and exceeds the rated sensitivity.

6. Independent of power supply and line voltage, and free from external interference, voltage fluctuation.


ItemRCCB , RCD
ModelA,AC(Electro-magnetic type,electronic type)
Pole2P,4P
Rated making and breaking capacity:630ARated voltage: 240/415V AC
Rated frequency:50/60Hz
Rated residual operating current10mA 30ma 100A 300mA
Tripping durationinstantaneous tripping 0.1s
Electro-mechanical enduranceMore than 4000 cycles
StandardIEC61008.1
Rated current(A)16,25,32,40,63
Installation35MM DIN RAIL

Residual tripping characteristics

Type AC

For which tripping is ensured for residual sinusoidal alternating currents, whether suddenly applied or slowly rising.

Type A
For which tripping is ensured for residual sinusoidal alternating currents and residual pulsating direct currents whether suddenly applied or slowly rising

Type S
For selectivity, with time-Delay