Add to Cart
Quiet Diesel Generator 100KVA Powered By Cummins Engine 6BT5.9-G2
Detailed Product Description
Silent Diesel Generator Set 100KVA Powered By Cummins Engine 6BT5.9-G2
Genset Data: 400/230V, 50Hz, 3 Phase 4 Pole, 1500RPM.
Product Description:
1. Prime power 100KVA, standby power 110KVA.
2. Powered by Cummins Engine.
3. Original Engga Alternator.
4. Delixi air breaker.
5. Electric start with Batteries.
6. Base integrated fuel tank.
7. Smartgen Controller.
8. ATS is for option.
Genset Specifications:
Genset model | SCE100 |
Genset rated power | 80KW/100KVA |
Rated voltage | 230/400V (adjustable) |
Rated current | 144 Amp |
Frequency | 50 Hz |
Power factor | 0.8 Lagging |
Connecting type | 3 phase 4 wire |
Cooling system | Closed cycle water-cooled with fan, water tank |
Overall dimension (L×W×H) mm | 2900×1150×1520 |
Gross weight (kg) | 1500 |
Engine Specifications:
Diesel Engine | |
Brand | DCEC CUMMINS |
Model | 6BT5.9-G2 |
Engine structure | 6 cylinders vertical in line,4 stroke, turbocharged |
Rotating speed | 1500 RPM |
Engine cooling method | Water-cooled |
Speed governing system | Electronic speed governor |
Starting method | By 24V batteries |
Engine filter system | Dry type air filter ,fuel filter, oil filter, water filter |
Displacement(L) | 5.9 |
Bore×Stroke(mm) | 102×120 |
Compression ratio | 17.5: 1 |
100% Load fuel consumption (litre/h) | ≤20.1 |
Lube capacity(L) | 16.4 |
Alternator Specifications:
Alternator | |
Brand | ENGGA |
Model | EG225-80N |
Excite type | Brushless self-excited AVR regulation |
Connecting type | 3 phase 4 pole |
Steady frequency change | 0.50% |
No load voltage | ≥95%-105% |
Steady voltage | ≤±1% |
Insulation class | Class H |
Protection grade | IP21 |
Manufacturing Standards:
ISO8528; ISO1105; ISO3046; GB/T2820; GB755; BS5000; NEMAMG-22; YD/T502
Electrical Parameters
Wave distortion: <10%
Voltage fluctuation: <0.5%
Voltage / frequency fluctuation: <=0.5%
AVR self-regulated, voltage regulation rate: <=+- 1%
Radio interference restraining accords with stipulation of
VDE0875-N and ISO8528
Control Function
Key start / auto start
Monitoring meters: Current; Frequency; Wire Voltage; Genset KVA;
Genset KW; Output
Capacity; Output KW.H; Power Factor.
Warning/Shutdown: Alternator Under/Over Volts, Frequency;
Under/Over Speed; Low Oil Pressure; High Engine Temp; High/Low
Battery Volts; Over Current; Earth Fault Shutdown.