AC120/240-6kW Rack Mounted Load Bank With 60HZ And Resisitive Power 6kW
Introduction
AC120/240-6kW Rack Mounted Load Bank , which can be used as terminal load test connectivity and reliability of power periodic line, safety of electric transmission line, battery.etc. Coordinate other power switchover. Also be used as simulate heat source of rack mounted server, test the air cooling system and air flow control.
Application
AC120/240-6kW Rack Mounted Load Bank With 60HZ And Resisitive Power 6kW
When building a data center, any unexpected glitch during commissioning can cause serious project delays, wasted productivity, and significant budget overruns. So integrating rack mounted load banks into the design phase can help our data center clients keep projects on budget and on time.
Technical specification
Parameter | |
Rated voltage/frequency | Single phase120/240VAC/60Hz |
Max Load Power | Resisitive Power: 6kW |
Load Resolution | Resistive Load: 3 steps. A circuit 2kW; B circuit 2kW;C2kW |
Power Factor | 1 |
Load Tolerance | +(0~10%) |
Insulation Grade | Grade F |
Way of Working | Continuous Working |
Cooling | Forced air cooling, intake air in front and exhaust cooling in back |
Case Color | Black |
Case Dimension | About 430mm*600mm*222mm(L×W×H) |
Weight | About 20 kgs About 18kgs |
Ambient Temperature ttTeTemperatureTemperature Temperature | -10℃~+40℃ |
Relative Humidity | ≤95% |
Altitude | ≤2500 meters |
Atmospheric Pressure | 86~106kPa |
(1) Load Test: User can load any power within rated power, and test the output capacity of under test power supply.
(2) Control Mode: load bank equip with voltage select switch and 3 load steps switch, can choose voltage by voltage select switch and control load/unload by 3 ABB air switch.
(3) Fan Power Supply: Fan is installed near the air outlet, and powered on A loop socket. Please give priority to the use A loop when using this load bank, the fan start after A loop is connected to power supply, then can load/unload through 3 gear air switches combination.
(4)Temperature Protection: There will be sound and light alarm when the load bank temperature exceeds the safety threshold value.
(5) Load bank Cable: The internal cable adopts multi core flame retardant flexible cord, and with glass fiber casing protection.