Add to Cart
Auto Testing Machine Usage And Use Electrical Load Testing
Equipment 400V 2000kw
Product Description
1. our load bank an accurately test output power and load capacity
with all kinds of generators.
2. System consists of testing/control and load bank, mainly
includes AC load bank, data capture system, auto load/unload
control system, heat dissipation device, assist control and PC
software.
Technical Parameter
Rating Voltage/Frequency | 400VAC/50Hz, 3 phase 4 wire, |
Rated Load Power | Resistive load: 2000kW |
Installed Capacity | Resistive load: 2000kW |
Load Step | 1,2,2,5,10,10,20,50,100,100,200kW*9, total 19 steps, |
PF(Power Factor) | 1 |
Load Tolerance (each step) | ±5% |
Load Tolerance(overall) | ±3% |
Display Precision | 0.5 class |
Control Power | 380VAC/50Hz, 3 phase 4 wire, |
Wire Connection | Load power supply input——Copper bar (star coupling) |
Insulation | F |
Protection Grade | IP21 |
Way of Working | Continuous Working |
Casing Dimensions and Cooling | about 4000*2350*2591mm (length*width*height) Forced air cooling,Horizontal inlet air,Vertical cooling |
Weight | About 5500kgs/set |
Transportation | Hoisting, there are lifting lug in top of casing |
Casing Color | Grey(RAL7035) |
Ambient Temperature | -10℃~+50℃ |
Relative Humidity | ≤95% |
Altitude | ≤1500 meter |
Atmospheric Pressure | 86~106kPa |
Contactor | Schneider |
Fuse | DELIXI |
MCU | INFINEON |
Data processing software | Kaixiang(self-developed) |
Alloy Resistance | Kaixiang(self-developed) |
Product Advantage
1 Local manual control: there is local control panel in load bank,
with multi load steps, min load steps 1kW, controlled by buttons.
2 Intelligent control: user can control load bank by data
processing software of PC to make automatic load/unload, display,
record and manager the test data, form curve, graph and can be
printed.
Control mode interlock: there is switch in control panel to choose
control mode, other control mode is invalid if user choose one
control mode.
Application
Load Banks are used with Engine Generators, Battery Systems, UPS
Systems, Inverters, Ground Power Units, Auxiliary Power Units,
Aircraft Power Generators, Wind Generators, and Hydro Generators.
It is used with Engine Generators, Battery Systems, UPS Systems,
Inverters, Ground Power Units, Auxiliary Power Units, Aircraft
Power Generators, Wind Generators, and Hydro Generators.