Add to Cart
On-Line Working Vacuum Transformer Oil Purifier Machine Transformer Oil Filtration Plant
I. Transformer Oil Centrifuge Machine Application
NSH VFD series On-Line Working Vacuum Transformer Oil Purifier Machine Transformer
Oil Filtration Plant is mainly used to improve the properties of insulation oil by
removing trace water, gas, particulate matters etc. from the
insulating oil effectively and rapidly. It is suitable for
purifying branded oil, insulating oil of high voltage and super
high voltage transformer.
II. Description
VF series-- Single-Stage Vacuum Insulation Oil Filtration Machine
VFD series-- Double-Stage Vacuum Insulation Oil Filtration Machine
VFD-R series-- Double-Stage Vacuum Insulation Oil Regeneration Filtration Machine
NSH VFD series utilizes coacervation technology,coalescing technology,separating technology and refined purification technology.Comparing to Model VF series,it add ROOTS Vacuum system,second stage of separating system to improve the effect of purification. To remove free,soluble water,carbon,free and dissovled gases and particulate matters from insulating oil effectively and rapidly.
For the treatment of aging transformer oil and deteriorated transformer oil, we recommend VFD-R series to regenerate them.
III. Features
IV. Available Style
1. Fixing type,mobile type with four wheels and mobile type with
trailer.
2. Normal appearance type,shelf-covering type and explosion-proof
type.
3. Avaliable in different color.
V. Technical Specification
Technical Specification | |||||||||
Item | Unit | VFD-30 | VFD-50 | VFD-80 | VFD-100 | VFD-150 | VFD-200 | VFD-300 | |
Flow Rate | L/H | 1800 | 3000 | 4800 | 6000 | 9000 | 12000 | 18000 | |
Vacuum Range | Mpa | -0.092 ~ -0.099 | |||||||
Working Pressure | Mpa | ≤0.2 | |||||||
Max Vacuum Range | Pa | ≤50 | |||||||
Temperature Range | ℃ | 45 ~ 65 | |||||||
Breakdown Voltage | Kv | ≥75 | |||||||
Impurity Size | μm | ≤5 | |||||||
Dielectric Loss | Tg | ≤0.005 | |||||||
Interfacial Tension | mn/m | ≥40 | |||||||
Water Content | PPM | ≤4 | |||||||
Gas Content | % | ≤0.1 | |||||||
Power Supply | 380V/3P/50Hz(or as needed) | ||||||||
Working Noise | dB(A) | ≤72 | ≤78 | ||||||
Heating Power | Kw | 30 | 48 | 72 | 90 | 120 | 180 | 240 | |
Total Power | Kw | 35 | 54 | 77 | 98 | 129 | 189 | 254 | |
Pipeline Diameter | mm | DN25 | DN32 | DN32 | DN40 | DN50 | DN65 | DN65 | |
Net Weight | Kg | 550 | 850 | 1000 | 1100 | 1400 | 1600 | 2200 | |
Size | length | mm | 1500 | 1500 | 1700 | 1900 | 2100 | 2100 | 2600 |
width | mm | 1200 | 1200 | 1500 | 1400 | 1550 | 1550 | 1800 | |
high | mm | 1750 | 1750 | 1850 | 1800 | 1900 | 1900 | 2000 |
VI. Relative Series:
VFD series: Insulation oil purifier System specialize in purifying branded
oil, insulation oil of high voltage and super high voltage
transformer. Additionally, it is suitable for treating low
viscosity lubrication oil.
TF series: Turbine oil purifier system is particularly suitable for
purifying turbine lubricating oil. It also applys to treat
hydraulic, coolant oil and other lubrication in which contain large
of water, vapor, impurities, sludge, dielectric and colloid. It can
eliminate them effectively and efficiently.
LV series: Lubrication Oil Filter System are suitable especially for
purifying and restoring hydraulic oil, machine oil, coolant oil and
various other lubrication oil.
GER series: Used oil regeneration system is suitable to regenerate used
internal-combustion engine oil including diesel engine oil,
gasoline engine oil, and used hydraulic oil, other used lubrication
oil of machinery.
GED series: it is used to recycle all kinds of waste oil into base oil or diesel oil with high quality.