Add to Cart
3000LPH Mobile Transformer Insulating Oil Purifier Single Axle,Used Transformer Oil Regeneration System
I. Description of transformer insulation oil purifier
VFD Series insulation oil purifier is mainly used for dealing with unqualified transformer oil, switch oil, mutual inductor oil, it can rapidly remove water, gas, particles from oil, improving insulating oil's properties.
II. Another models of transformer oil purifier
VF series-- Single-Stage Vacuum Insulation Oil Filtration Machine
VFD series-- Double-Stage Vacuum Transformer Oil Filtration Machine
VFD-R series-- Double-Stage Vacuum Insulation Oil Regeneration Filtration Machine
III. Insulation oil purifier machines' advantages
1. Double-stage vacuum system, strong power of vacuum evacuating,
ultimate vacuum value ≤ 5Pa.
2. Two vacuum separating chambers, efficient oil film sprayer,
increasing separating size and separating time to ensure the
dry-level and dielectric strength improving greatly.
3. Duplex-Stereo film evaporation technology, combined with unique
and advanced dewatering, degassing components, can rapidly and
effectively separate water, gas from oil.
4. Multi-stage precision filtration system, mesh filtration
combined with molecular adsorption technologies.
5. Efficient electric heating system, heating uniformity, less
power consumption, safe, and reliable.
6. Double-infrared liquid level sensor, pressure protective system
to ensure machine operation easy and safely.
IV. Available Options
1. Normal appearance type,shelf-covering type and explosion-proof
type.
2. Fixing type,mobile type with four wheels and mobile type with
trailer.
3. Avaliable in different color.
V. Technical Specification
Technical Specification | |||||||||
Item | Unit | VFD-30 | VFD-50 | VFD-80 | VFD-100 | VFD-150 | VFD-200 | VFD-300 | |
Flow Rate | L/H | 1800 | 3000 | 4800 | 6000 | 9000 | 12000 | 18000 | |
Vacuum Range | Mpa | -0.092 ~ -0.099 | |||||||
Working Pressure | Mpa | ≤0.2 | |||||||
Max Vacuum Range | Pa | ≤50 | |||||||
Temperature Range | ℃ | 45 ~ 65 | |||||||
Breakdown Voltage | Kv | ≥75 | |||||||
Impurity Size | μm | ≤5 | |||||||
Dielectric Loss | Tg | ≤0.005 | |||||||
Interfacial Tension | mn/m | ≥40 | |||||||
Water Content | PPM | ≤4 | |||||||
Gas Content | % | ≤0.1 | |||||||
Power Supply | 380V/3P/50Hz(or as needed) | ||||||||
Working Noise | dB(A) | ≤72 | ≤78 | ||||||
Heating Power | Kw | 30 | 48 | 72 | 90 | 120 | 180 | 240 | |
Total Power | Kw | 35 | 54 | 77 | 98 | 129 | 189 | 254 | |
Pipeline Diameter | mm | DN25 | DN32 | DN32 | DN40 | DN50 | DN65 | DN65 | |
Net Weight | Kg | 550 | 850 | 1000 | 1100 | 1400 | 1600 | 2200 | |
Size | length | mm | 1500 | 1500 | 1700 | 1900 | 2100 | 2100 | 2600 |
width | mm | 1200 | 1200 | 1500 | 1400 | 1550 | 1550 | 1800 | |
high | mm | 1750 | 1750 | 1850 | 1800 | 1900 | 1900 | 2000 |
VI. Another types of our oil purifier machines
TF series: Turbine oil purifier system is particularly suitable for
purifying turbine lubricating oil. It also applys to treat
hydraulic, coolant oil and other lubrication in which contain large
of water, vapor, impurities, sludge, dielectric and colloid. It can
eliminate them effectively and efficiently.
LV series: Lubrication Oil Filter System are suitable especially for
purifying and restoring hydraulic oil, machine oil, coolant oil and
various other lubrication oil.
GER series: Used oil regeneration system is suitable to regenerate used
internal-combustion engine oil including diesel engine oil,
gasoline engine oil, and used hydraulic oil, other used lubrication
oil of machinery.
GED series: it is used to recycle all kinds of waste oil into base oil or diesel oil with high quality.