Medium Voltage 36.5kV Column Mounted Metering Box 2VT 2CT

Brand Name:Chuangyin
Certification:KEMA/type test report
Model Number:OMS-15,OMS-25,OMS-36
Minimum Order Quantity:1 pc
Delivery Time:5-10 workdays
Payment Terms:L/C, T/T
Contact Now

Add to Cart

Verified Supplier
Location: Shenzhen Guangdong China
Address: 1st Floor, B Block, Jiada R&D Building, Nanshan, Shenzhen, China
Supplier`s last login times: within 13 hours
Product Details Company Profile
Product Details

OMS-15,OMS-25,OMS-36

Overhead pole mounted primary metering unit

1. Product introduction

1.1 Product type name and model: 15.5-36.5kV medium voltage overhead column mounted metering box and JLSZXW7-15/25/36 type combined transformer.

1.2 Product overview:

This type of metering box is an outdoor dry three-phase primary metering unit. The medium voltage metering transformer is assembled by up to 3 single-phase current transformers and 3 single-phase voltage transformers. The transformer adopts cycloaliphatic epoxy resin (CEP) vacuum casting solid encapsulation, which has excellent insulation performance and hydrophobicity. The surface is resistant to acid and alkali corrosion, pollution, and UV. It is suitable for outdoor overhead line installation and connection to public power systems. The metering box can be equipped with a metering meter box. All the secondary leads of the transformer can be connected and collected in the meter box. It is also equipped with a test terminal block and a meter installation space. The meter can be configured according to the requirements or the user can configure the meter. After connecting it, it can be used for electric energy measurement, current and voltage measurement in urban and rural power distribution network lines with the highest voltage of 15.5/25.5/36.5kV and below.


1.3 Basic parameters:

No.ItemUnitsSpecification
1.Maximum system
voltage (kV, rms)
kV15.525.536.5
2.rated frequency (fR)Hz50, 60 or 50/60
3.

Rated lightning impulse
withstand voltage (peak)


kV95kV,110 kV125 kV,150 kV200 kV
4.Rated power-frequency
withstand voltage on primary
kV345070
5.

Rated power-frequency
withstand voltage on secondary


kV2.5
6.Number of CTs and VTspcs3VT+3CT ,3VT+2CT,2VT+2CT
7.Standard/

IEEE(ANSI) C57.13-2006

IEC 61869-1:2007, IEC 61869-2:2012

IEC 61869-3:2011,IEC 61869-4:2013


2. Product function and use:

Overhead pole mounted primary metering unit need to be complied with the latest applicable industry standards and local and/or national electrical regulations (IEC, IEEE (ANSI), CAN, GOST, CEF). It is used for three-phase overhead power grid energy measurement management and distribution network automation management system. The primary side measurement is more accurate, and the power loss of the line can be effectively measured to reduce losses.


3. Main features of the product:

1. The medium voltage transformer of the metering unit can be assembled by up to 6 single transformers, which can be flexibly disassembled and assembled as required when shipped. It can be installed directly on the pole outdoors, which is convenient and quick;

2. The metering unit can be equipped with a meter box as required and connected to the transformer connection. The meter installation space is reserved in the box, and the door lock seal structure is designed to prevent electricity theft.

3. The meter box body is made of corrosion-resistant stainless steel or low-carbon steel of the same performance and the sealing design is weather-proof. The surface is coated with an anti-corrosion paint powder layer, which is resistant to acid and alkali corrosion and UV;

4. The medium voltage combined transformer is insulated with epoxy resin solid encapsulation,. The surface is dirt-resistant and UV-resistant which has excellent dielectric and mechanical properties. It is oil-free, gas-free and maintenance-free that can meet the requirements of safe operation and environmental protection;

5. The CT of the medium voltage combined transformer can be configured with dual ratios. The VT is equipped with anti-short circuit and overload protection design to avoid burning and explosion caused by VT short circuit and overload.

6. The one-time connection adopts NEMA contact bar and wiring clamp connection. The wiring terminals of the corresponding area can be configured according to user requirements. Lightning arresters can be selected as required.


4. Product Specifications:

Current transformer specifications

NoItem规格参数
1.Rated primary current5A up to 800A
2.Rated secondary current5A或1A
3.Rated Continuous Thermal Current150%,200%,300% etc.
4.Rated Short time current (Ith) (thermal 1 second)80xIpr
5.Rated Dynamic Current (Idyn)2.5xIth
6.Rated burdenB-0.1,B-0.2,B-0.5,B-0.9
7.Accuracy Class0.15S,0.15,0.3,0.6,1.2 Metering
8.Applicable StandardIEEE C57.13-2006

Voltage transformer specifications

NoItemSpec.
1.Rated primary voltage(V)

7200,

77620,

8400, etc.

12000,

13200,

14400, etc.

34500/√3,

20125, etc.

2.Rated secondary voltage(V)110/√3,115/√3, 120/√3, 110,115,120
3.Rated Voltage Factor

1.1/Continuous

1.25/8h,1.4/1min.,1.5/1min.,1.73/1min.

1.5/30s,1.9/30s,1.9/8h

4.Standard connectionY-Y connection for 3CT+3VT
5.Rated burdenW,X,M,Y,Z
6.Accuracy Class0.15,0.3,0.6,1.2 Metering
7.Thermal burden(VA)500,750,1000,1200,1500,etc.
8.Applicable StandardIEEE C57.13-2006

Note: If the parameters required by the user exceed the range of the above table, it can be determined after consultation with our company.


5. Product dimensions and wiring schematic diagram:

OMS-15 Appearance dimension drawing


OMS-25 Appearance dimension drawing


OMS-36 Appearance dimension drawing


Optional meter box 1 (ANSI) size can be made as required


Optional meter box 2 (IEC) size can be made as required


Wiring diagram


6. Special requirements

Other specifications are available as per clients’ requests.


China Medium Voltage 36.5kV Column Mounted Metering Box 2VT 2CT supplier

Medium Voltage 36.5kV Column Mounted Metering Box 2VT 2CT

Inquiry Cart 0