Add to Cart
Peakmeter Photovoltaic System Solution:Peakmeter Photovoltaic System Solution.pdf
Specifications | Function | Range |
3 pole & 4 pole earthing-resistance test | Test voltage | AC 20V/48V |
Test frequency | 94Hz/105Hz/111Hz/128Hz/AFC | |
Earthing-resistance | 0.02Ω~300kΩ | |
3 pole & 4 pole with Current Clamp | Test voltage | AC 20V/48V |
Test frequency | 94Hz/105Hz/111Hz/128Hz/AFC | |
Earthing-resistance | 0.02Ω~20kΩ | |
Non-auxiliary-polar mode (Double Clamps) | Test voltage | AC 48V |
Test frequency | 94Hz/105Hz/111Hz/128Hz/AFC | |
Earthing-resistance | 0.02Ω~150Ω | |
2 pole R~ | Test voltage | AC 20V |
Test frequency | 94Hz/105Hz/111Hz/128Hz/AFC | |
Earthing-resistance | 0.02Ω~300kΩ | |
2 pole or 4 pole R | Test voltage | DC 20V |
Earthing-resistance | 0.02Ω~300kΩ | |
Interfering voltage/ current/ frequency | Interfering voltage | 1~50V DC/AC |
Interfering frequency | 16HZ~400Hz | |
Interfering current | 20mA~2A | |
Soil resistivity | Test voltage | AC 20V/48V |
Test frequency | 94Hz/105Hz/111Hz/128Hz/AFC | |
Range | 0.02Ω*m~1000kΩ*m | |
RK (Wire compensation) | Test voltage | AC 20V/48V |
Test frequency | 94Hz/105Hz/111Hz/128Hz/AFC | |
Range | 0.02Ω~30Ω | |
Features | ||
Display | 9999 counts | |
Test voltage have 20V/48V choice | √ | |
2 pole resistance measurement | √ | |
3 pole & 4 pole earth resistance measurement | √ | |
Soil resistivity testing | √ | |
Auto power off | √ | |
Setting and time | √ | |
Review and delete the held data | √ | |
Data storage | 100 groups | |
Reviewing and Deleting Saved Data | √ | |
PC Communication | √ | |
General | ||
Power Supply | 10*1.5V LR14 Batteries | |
Size | 260mm*125mm*280mm | |
Clamp Size | φ51mm | |
Weight | 2.5Kg | |
Safety Rating | EN61010-1, EN61010-031, EN61326-1, CAT Ⅲ 300V |
MS2308 is an advanced earthing-resistance testers integrated with multiple measuring methods, can be used for checking earthing-resistance of transformer, anti-lightning system, high-voltage power tower, and communication equipment, and its automatic frequency control (AFC) function can bring interference to an absolute minimum.