High Voltage Resonant Test System
500KV 50HZ AC High Voltage Resonant Test System For Substation
This series devices are designed for AC withstand voltage test of substation primary equipment under 550KV or below, mainly composed of variable-frequency power supply, exciting transformer, reactor and capacitive Voltage divider.


Features

1. Easy to operate, two working modes: manual and automatic.

2. Can set Test Voltage, frequency range, protective current and operating time.

3. Smaller size, lighter weight compared with same voltage level same capacity reactor.

4. Small temperature rise at rated load. Strong protection, good stability. Multiple functions, cost effective.

5. Dry type epoxy cast, high mechanical strength, good insulation, nice and reliable.

6. Adjustable capacity of frequency control source.

7. With 220V or 380V single phase power, convenient for on-site power sourcing.

8. Flexible configuration. Different type reactors for option to meet different test object requirements.



Technical Indicators

1. Rated output voltage: 0 - 1000kV, output frequency: 30 ~ 300Hz.Waveform: pure sine wave, THD <1.0%.

2. Duty Cycle: Continuous working time 60mins one time at full power output.

3. Quality factor: 30-90. Frequency adjustment sensitivity: 0.1Hz, instability <0.05%.

4. Power Supply: 380/220V±15%, 50Hz ± 5%.


Rated output voltage0 - 1000kV
output frequency30 ~ 300Hz
Waveformpure sine wave
THD<1.0%.
Duty CycleContinuous working time 60mins one time at full power output
Quality factor30-90
Frequency adjustment sensitivity0.1Hz, instability <0.05%.
Power Supply380/220V±15%,
Power frequency50Hz ± 5%.