Thermal Terminal PE Heat Shrinkable Cable Accessories

Brand Name:HICORPWELL
Certification:ISO9001-2015
Model Number:Thermal Shrinkable Terminal Head
Minimum Order Quantity:10sets
Payment Terms:Western Union, L/C, T/T
Place of Origin:China
Contact Now

Add to Cart

Site Member
Location: Shenzhen Guangdong China
Address: Rm 604 Bldg 9th Yinxingyuan South Rd Nanshan District 518054 Shenzhen China
Supplier`s last login times: within 28 hours
Product Details Company Profile
Product Details

Customized International Standard Heat shrinkable cable accessories Thermal terminal


The installation of the heat shrinkable cable accessories must be a complete continuous construction, so as not to be affected with damp be affected with damp, 10 kv and below cable heat appears should be completed within four hours. C .


Type heat shrinkable power cable accessories has small volume, reliable performance, strong adaptability,

simple and easy for installation.


Applicable to power cable households inside and outside the terminal and intermediate links.


The end of the insulation tube is generally 650mm, but can also be extended to


800mm, 1000mm, 1200m.(according to the requirements of customers).


Before making cable head, need special tools to be complete, construction personnel


should be familiar with the use of various instruments, inspection, and matters needing attention.


The steel armor ground wire and copper screen ground wire separately,


making the cable pre-test more convenient and reasonable.


Product specification


Product NameTypecable section(mm2)
10kv three-core XLPE cable indoor terminationHCW-10/3.125-50
HCW-10/3.270-120
HCW-10/3.3150-240
HCW-10/3.4300-500
10kv three-core XLPE cable outdoor terminationHCW-10/3.125-50
HCW-10/3.270-120
HCW-10/3.3150-240
HCW-10/3.4300-500
10kv three-core PILC cable indoor terminationHCW-10/3.125-50
HCW-10/3.270-120
HCW-10/3.3150-240
10kv three-core PILC cable outdoor terminationHCW-10/3.125-50
HCW-10/3.270-120
HCW-10/3.3150-240

Technical Index


Product Name

10KV heat
shrinkable
termination

and joint

Sr. No.Test NameStandard RequirementResultRemarks
1Power frequency
withstand voltage test
(wet)

39kv,5min,neither flashover

nor breakdown occurs

39kv,5min,neither flashover nor
breakdown occurs
Pass
2Partial discharge test15kv,the magnitude of discharge shall not exceed 10pc15kv,the magnitude of discharge is 1.5pcPass
3Load cycling test at
constant voltage
heating 5h,cooling 3h,heating
conductor to
heating 5h,cooling 3h,heating conductor
to 75℃
Judged by
following
tests
4Impulse voltage test95kv,10 positive and 10 negative
impulses, neither flashover nor
breakdown occurs
10 positive and 10 negative
impulses, neither flashover nor
breakdown occurs
Pass
54h power frequency
withstand voltage test
35kv,4h,neither flashover nor
breakdown occurs
35kv,4h,neither flashover nor breakdown
occurs
Pass


China Thermal Terminal PE Heat Shrinkable Cable Accessories supplier