Add to Cart
NO | Items | Characteristics | |
2.1 | Normal capacity | 100Ah | |
2.2 | Nominal energy | 1.28KWh | |
2.3 | Nominal voltage | 12.8V (LFP-4S) | |
2.4 | Internal resistance | ≤20mΩ @1kHz AC | |
2.5 | Normal charge voltage | 14.6±0.2V | |
2.6 | Float charge voltage(for Standby use) | 13.8±0.2V | |
2.7 | Allowed MAX charge current | 100A | |
2.8 | Recommended charge current | ≤50A | |
2.9 | Allowed MAX discharge current | 100A | |
2.10 | End of discharge voltage | 10.0V | |
2.11 | Dimension | Width 350±3 mm | |
Height 188±3 mm | |||
Deepness 176±3 mm | |||
2.12 | Weight (No accessories) | About: 11Kg | |
2.13 | Operation temperature | Charge | 0~45℃ |
Discharge | -20~60℃ | ||
2.14 | Self-discharge rate | Residual capacity | ≤3%/Month; ≤15%/ year |
Recover capacity | ≤1.5%/Month; ≤8%/ year | ||
2.15 | Storage environment | ≤1month | 20~+60℃, 5~75%RH |
≥3month | -10~+45℃, 5~75%RH | ||
Recommend environment | 15~35℃, 5~75%RH |
NO | Items | Criterion | Condition | |
3.1 | Normal Capacity | 100Ah | After Normal charge, discharge @0.33C current to the end of discharge voltage. | |
3.2 | Internal Impedance | ≤20mΩ | @50% SOC @1kHz AC internal resistance test instrument. | |
3.3 | Short circuit protection | Auto cutoff load when short circuit | Connect the positive and negative of this battery pack through a lead with 0.1Ω resistance. | |
3.4 | Cycle life @DOD100% | ≥2000 cycles | After Normal charge,discharge @0.33C current to the end of discharge voltage. Repeat above process until discharge capacity reduce to 80% of initial value. | |
3.5 | Discharge temperature | -20℃(6h) | ≥70% |
|
0℃(6h) | ≥80% | |||
25℃(4h) | ≥100% | |||
55℃(4h) | ≥95% | |||
3.6 | Capacity retention rate | remain capacity | After normal charge, store the battery @25±5℃ for 28days, then discharge capacity @0.33C,the retention capacity accord with criterion. |