Fire gas extinguisher cabinet FM200 extinguishing systems 120kg
Cabinet FM200 fire extinguishing installation is included cylinder, jet pipeline, nozzle, valve actuator, such as
collection in one. Could connect with auto fire alarm gas control
panel, and automatic detect and fire extinguishing.
Specification:
Item | Max filing | 20℃storage pressure(MPa) | Jet time(S) | Work.Temp (℃) | Magnetic valve work voltage | Max protection | Dimension (mm) |
GQQ70/ 2.5C | 70 | 2.5 | ≤10 | 0~50 | 24VDC | 106 | 502X453X1530 |
GQQ90/ 2.5C | 90 | 136 | 552X453X1690 | ||||
GQQ120/ 2.5C | 120 | 182 | 602X503X1580 | ||||
GQQ150/ 2.5C | 150 | 227 | 702X573X1635 |
Application:
1 combustible gas fire;
2 combustible liquid fire;
3 combustible solid surface fire;
4 electrical equipment fire;
Also widely used in electronic computer room, disk, paper tape
libraries, electronic control equipment room, communications
center, television microwave room, library, rare and precious
cultural relics museum, archives, fuel oil boiler room, power
transformer room, high voltage capacitor room, oil switch room and
other expensive equipment such as buildings.Relative to that of other fire extinguishing system for the main
scope of application is:
1 valuables priceless treasures or company data files and software;
2 no sprinkler system or the use of water can cause water damage of
equipment;
3 personnel resident area;
4 storage space between the cylinder of fire extinguishing agent is
limited, should be a small amount of fire extinguishing agent,
which can achieve the fire extinguishing efficiency.
Working principle and control and operation:
1, Put the selection button of control panel to "automatic", the fire
extinguishing system in a state of automatic control. When the fire detector give alarm signal, fire alarm control panel
will send out sound and light alarm, and send a joint order, close
linkage device, after 0 to 30 s, fire extinguishing order send out,
the electromagnetic valve action, and the FM200 cylinder valves
open,FM200 through the connecting hose, nozzle discharge and fire
extinguishing protection zone.
2, Electrical manual startup control:Put the selection button of control panel to "manual", fire extinguishing system in a state of manual control.When the fire happen, can press the start button on manual control
panel or control panel according to the prescribed procedures to
start the fire extinguishing system release FM200 and fire
extinguishing.In the automatic control state, still can realize electric manual
control.
3, Mechanical emergency start control:When the fire happen, the control panel cannot give fire
extinguishing order,should notify the relevant personnel to
evacuate the scene, close linkage device, and then pull out the
insurance on the electromagnetic valve pin, panting manual button
to open the bottle of head valve, release FM200 and fire
extinguishing.
4, When the fire alarm found to have abnormal situation in the delay
time, do not need to start the fire extinguishing system, according
to the manual control box or emergency stop button on the control
panel, can stop control panel send fire extinguishing order.