GE Multilin FM2 Feeder Manager 2 FM2-722-PD Switch Control Power
240VAC Universal Relay
Product Description : Multilin FM2 Feeder Manager 2
Model | FM2-722-PD |
Supply voltage | 120/140 Vac |
Maximum cintact rating | 250VAC 10a Resistive |
Models
The FM2 has 4 models. All models contain three phase thermal
overload protection (49/51), earthfault protection (50G),
undervoltage reclose, current, voltage, power and energy metering,
timersand counters, 6 control inputs (Close A, Close B, Open, Test
Mode, Contactor A status, Contactor BStatus), plus 10 programmable
inputs, separate outputs dedicated to two different
contactors/breakers, one programmable output, and an ESD (emergency
shutdown) output. The relay unit canbe powered up by 120/240 V AC,
50 or 60 Hz.
FM2-712-PD. This model comes with a 2 line 40 character LCD display, keypad
and status indi-cating LEDS. The VT input and switch input voltage
is rated for 120 V AC.
FM2-722-PD. This model comes with a 2 line 40 character LCD display, keypad
and status indi-cating LEDS. The VT input and switch input voltage
is rated for 240 V AC.
FM2-712-C. This is a black box version of FM2 with no display, keypad or
status indicating LEDS. The VT input and switch input voltage is
rated for 120 V AC.
FM2-722-C. This is a black box version of FM2 with no display, keypad or
status indicating LEDS. The VT input and switch input voltage is
rated for 240 V AC
Features
Feeder contactor/breaker operation.
The relay has ability to control both contactor and breaker
feeders. For feeders that use a contactor,either of the outputs,
Relay A or Relay B, can be used to control the contactor. For
feeders usingbreakers, the output Relay A is used for closing the
breaker and the output Relay B is used fortripping the breaker.
Refer to the FM2 instruction manual (GEK-106559) for additional
information.
Thermal overload protection.
The relay offers three overload curves (IEC A, IEC B and IEC C)
defined in IEC 255-4 and Britishstandard BS142. The curve
multiplier setpoint (0.5 to 1.0) allows shifting of the selected
base curvein the vertical time direction. Refer to the thermal
protection sections of the FM2 instruction manual(GEK-106559) for
additional information.
Earth fault protection.
The relay provides instantaneous earth fault protection. The earth
fault current can be detectedeither from the residual connection of
the phase CTs or from the zero sequence CT. A delay time canbe set
to prevent false alarms from momentary surges. Delay can be
provided to earth fault trips aswell to co-ordinate other relays in
the system. Refer to the FM2 instruction manual (GEK-106559)for
additional information.
Contactor/circuit breaker failure.
The relay provides contactor/circuit breaker monitoring while
performing close and opencommands. If the contactor does not change
status an 'open control circuit' or 'welded contactor'alarm is
triggered. If the breaker does not change status an 'breaker failed
to close' or 'breakerfailed to open' alarm is triggered.
Undervoltage auto reclose.
The feeder can be automatically reclosed after a momentary power
loss when this feature isenabled. When the control voltage drops
below the dropout voltage the contactors are de-energized. The FM2
can initiate timers to reclose the contactor upon the return of
supply voltage. Ifcontrol voltage is restored within the programmed
reclose time, the feeder will be reclosedimmediately. If the
control voltage takes longer to be restored, the FM2 can be
programmed to attempt a reclose after a set time delay. The
programmable reclose delay can be set independentlyfor two
programmable reclose power loss delays. Refer to the FM2 manual
(GEK-106559) foradditional information.
Metering.
The relay displays following metering information: Phase RMS
currents and Earth leakage current,Phase current imbalance in
percent (%), VT Primary Voltage, Power and Energy (if VT primary
isprogrammed).
Monitoring.
The relay monitors number of contactor/breaker operations and
feeder operation time. It displaysthe following information: No. of
operations, Total trips, Earth fault trips, Number of Control
trips,Number of Hours feeder closed, Number of hours feeder closed
since last closed, Number of hoursfeeder open. This information can
be reset to zero by giving clear timer and clear countercommands.
Device information.
The device details such as firmware, supervisor program and boot
program versions, order code,date of manufacture, serial number is
available under factory data setpoints. For more information,refer
to the Factory Data section of the FM2 manual (GEK-106559).
enerVista FM2 Setup software
The enerVista FM2 setup software allows immediate access to all the
features of the FM2 throughpull-down menus in the familiar Windows
environment. The software can also run without a FM2connected. This
allows you to edit and save setpoint files for later use. If a FM2
is connected to aserial port on a computer and communication is
enabled, the FM2 can be programmed from thesetpoint screens. In
addition, measured values, status and alarm messages can be
displayed withthe actual screens.
Upgrading Product Firmware/Software
Packaging & Delivery
Packaging Details
Cartons
Delivery Time
Whithin 3-5 days
Company Introduction
Our advantage Products:
【Honeywell】Module DCS / PLC
【Emerson / Delta V】Module
【ABB】Input Output Module
【AB】Module / Touch Screen
【Rosemount】Pressure and Temperature Transmitter
【Yokogawa】Pressure Transmitter
【Yaskawa】Servo Drive / Servo Motor
【GE/Fanuc】IC69 Series PLC
【Mitsubishi】Servo Drive / Servo Motor
(Modicon,SMC,SICK,NORGREN,Siemens etc.)