Add to Cart
2P 800 Volt DC MCCB for Moulded Case Circuit Breaker Mini Circuit Breakers
Model | ERM1L-125 | ERM1L-250 | ||||
Current level of frame Inm(A) | 125 | 250 | ||||
Rated current(A) | 16,20,25,32,40,50,63,80,100,125 | 100,125,140,160,180,200,225,250 | ||||
Rated operational voltage Ue(V) | AC400V | |||||
Rated insulation voltage Ui(V) | AC800V | |||||
Number of poles | 3 | 4 | 3 | 4 | ||
Level of rated limit short circuit breaking capacity | M | H | M | H | ||
Rated residual action current I△n Type I | 100,300,500 mA | 100,300,500 mA | ||||
Rated residual action current I△n Type II | 30,100,300 mA | 30,100,300 mA | ||||
Rated residual non action current | I△n x 50% | |||||
Rated resudual short circuit connecting(breaking) capacity I△n(mA) | Icu x 25% | |||||
Rated limit short circuit breaking capacity Icu(kA) AC400V | 50 | 85 | 50 | 50 | 85 | 50 |
Rated service short breaking capacity Ics(kA) AC400V | 35 | 50 | 35 | 35 | 50 | 35 |
Operational performance(times) Power on | 3000 | 2500 | ||||
Operational performance(times) Power off | 7000 | 6500 | ||||
Flashover distance(mm) | <=50 | <=50 |
Model | ERM1L-400 | ERM1L-630 | ||||
Current level of frame Inm(A) | 400 | 630 | ||||
Rated current(A) | 200,225,250,315,350,400 | 400,500,630 | ||||
Rated operational voltage Ue(V) | AC400V | |||||
Rated insulation voltage Ui(V) | AC800V | |||||
Number of poles | 3 | 4 | 3 | 4 | ||
Level of rated limit short circuit breaking capacity | M | H | M | H | ||
Rated residual action current I△n Type I | 100,300,500 mA | 100,300,500 mA | ||||
Rated residual action current I△n Type II | 300,500,1000 mA | 300,500,1000 mA | ||||
Rated residual non action current | I△n x 50% | |||||
Rated resudual short circuit connecting(breaking) capacity I△n(mA) | Icu x 25% | |||||
Rated limit short circuit breaking capacity Icu(kA) AC400V | 65 | 100 | 65 | 65 | 100 | 65 |
Rated service short breaking capacity Ics(kA) AC400V | 42 | 65 | 42 | 42 | 65 | 42 |
Operational performance(times) Power on | 1500 | 1500 | ||||
Operational performance(times) Power off | 4000 | 4000 | ||||
Flashover distance(mm) | <=100 | <=100 |