In the packaging industry, after the plastic packaging is heated,
the food and medicine on the production line need to be packaged.
The chiller can reduce the temperature to the appropriate packaging
temperature in the shortest time, thereby greatly improving the
work efficiency.
Central chiller specification
Model | AGS-085ASH | |
Nominal cooling capacity | kcal/h | 218440 |
kw | 254 | |
Input power | kw | 88.7 |
Max. Running current | A | 201.3 |
Power supply | 3PH~380V/60HZ | |
Refrigerant | type | R407 |
refrigerating circuit | 1 | |
type of control | thermostatic expansion valve | |
Compressor | type | semi-hermetic screw |
quantity | 1 | |
Condenser | Power | 75.2 |
start-up mode | Y-△ | |
capacity control | 0-25-50-75-100 | |
Fan | type | air cooled type finned copper tube |
cooling air flow (m3/h) | 91000 | |
power(kw) | 13.5 | |
Evaporator | type | shell and tube |
quantity | 1 | |
chilled fluid flow (m3/h) | 47.8 | |
inlet and outlet pipe diameter (inch) | 4 | |
Safety protection | compressor over temperature, unit overload, high and low pressure, flow switch, phase sequence, phase-missing, anti-freezing | |
Net weight | kg | 2420 |
Dimension | mm | 3150*2140*2200 |
Features of Anges air-cooled screw industrial chiller
Why air-cooled chiller has high pressure alarm?
In hot summer, many air-cooled chillers have high pressure
alarm,especially in areas with relatively high temperatures which
can be above 45℃, such as Saudi Arabia, the United Arab Emirates,
Iraq and so on.
General air-cooled chiller is equipped with a full set of
protection devices, when the chiller appears high pressure alarm,
it will automatically start the protection device, and the
corresponding fault indicator light will be lit.
The high pressure alarm of the air-cooled chiller is triggered by
the poor cooling effect of the condenser.If this problem is not
fixed and keep running the chiller at high pressure for a long
time, it will cause the current to be too large and burn the
compressor.
The reasons for the chiller high pressure alarm are as follows:
1. Air-cooled chiller’s condenser rely on fans to dissipate
heat.When the ambient temperature is above 42 degrees, the heat
dissipation of the condenser is poor, that is, the heat generated
by the refrigerant circulation cannot be taken away by the fan.
2. The condenser is dirty and blocked, which will also cause poor
heat dissipation and lead to high pressure alarm.
Solution:
1. Check whether the fan works properly.
2. Make sure there’s good ventilation to exhaust hot air smoothly.
3. If the ambient temperature is higher than 42 degrees, use a fan
or cooler to cool down the temperature around.
4. Periodically remove the air filter to clean the fins or clean
the fins with high-pressure air.
5. If the ambient temperature is around 42 ℃, need to increase the
condenser size to improve heat dissipation efficiency.Normally, we
will increase size to 25% for chiller using refrigerant R22, R407c,
R410a.
If ambient temperature higher than 45 ℃, we suggest to design the
chiller with R134a which can be used at ambient temperature of 50
℃.The disadvantage is that the cost is relatively high, because its
refrigeration efficiency is only 65% compare with other
refrigerants, in order to achieve the same cooling capacity, you
must use a larger compressor.
P.S. The installation of air-cooled chiller should choose the right
location to ensure that the installation environment is well
ventilated.
How to select the model of the chiller ?