Explosion Proof High-Performance Infrared Flame Detector For Transportation And Storage Facilities
Introduction
Infrared (IR) flame detectors are specialized sensors designed to detect the presence of flames by identifying the unique infrared light signature produced by combustion. These devices are widely used in industrial and commercial applications to provide early warning of potential fire hazards.
The primary working principle of an IR flame detector involves monitoring the infrared radiation emitted by flames. Flames generated by the combustion of various fuels, including hydrocarbon-based materials, produce a characteristic infrared radiation spectrum that can be detected by the sensor. This allows the detector to distinguish the infrared signature of a flame from other heat sources or ambient infrared radiation.
Suitable places
1. Transportation, storage, production and other places for
flammable goods;
2. Substation facilities, engine room, power station environments;
3. Places where open flames are strictly prohibited, such as
liquefied gas stations, garages, gas stations, etc
4. Harsh environment and other environment where the other kind
detectors are difficult to function.
Specifications
Working voltage | 18V-32VDC |
Interface | 4”(Φ20mm) explosion-proof hose |
Infrared Flame Detector Detection Angle | 90 degree |
Level of protection | IP66/IP65 |
Explosion Proof Level | Ex d lIC T6 Gb. Ex tD A21 IP66/IP67 T80℃ |
Alarm Status | ≤40mA/24VDC |
Fire response time | ≤10S |
Sensitivity | 1m-40m can respond(0.1 m-1.3m) |
Working environment | humidity ≤95%RH, no condensation |
Instruction
The green work indicator is steady on at the normal situation.
when the fire is found, The red alarm indicator is steady on. At
the same time, the fire alarm relay is closed and the yellow/white
lines are conductive, output the fire alarm signal.
The detector is a non-coding detector, which needs to connect the
interface module when it is connected to the bus system.
Wiring Instruction
Red/black: 24V power line
Yellow/white:Alarm relay ouput, it is closed, normally open.
Blue/green:Fault relay output, it’s open, normally closed.
Maintenance:
In order to keep in good work situation, it need arrange test to
the flame detector every 3 months at least. Once the detector is
damaged or not working properly, need to repaire or replace
accordingly.
Product range
Conventional Fire Alarm System
Addressable fire alarm system
Gas Extinguishing control system
Beam Detector
4 wire smoke detectors with relay output.
2 wire Conventional smoke and heat detectors
Explosion-proof flame detector for fire alarm system
Standalone smoke detectors and combustable gas detector