Add to Cart
The two-wire ultrasonic level meter is an instrument used to measure the level of liquid or solid materials. It is usually used in industrial automation, material monitoring and environmental management. Its working principle is to use the time difference of ultrasonic wave propagation in the medium to determine the liquid level. The device calculates the height of the liquid or the accumulation height of the material by emitting ultrasonic signals and receiving reflected signals.
Main features:
1. **Two-wire design**:
- Unlike traditional four-wire or three-wire level meters, the two-wire ultrasonic level meter uses two cables for connection: one cable for power supply and the other for signal transmission. The cable wiring and wiring are simpler, which can reduce installation and maintenance costs.
2. **High accuracy and high stability**:
- The level meter has high measurement accuracy and stability, and is suitable for various liquid level detection requirements.
3. **Contact-free measurement**:
- Because the measurement is carried out by ultrasonic wave, the liquid or material can be prevented from contacting the sensor, reducing the maintenance requirements caused by material corrosion, scaling and other problems.
4. **Wide Application**:
- Two-wire ultrasonic level meter can be widely used in level
measurement, especially for corrosive liquid, sewage treatment,
tank level monitoring, chemical storage and other fields.
5. **Strong Anti-interference Ability**:
- The device is designed with electromagnetic interference problems
in industrial sites in mind, and usually has strong
anti-interference ability and can work normally in complex
environments.
6. **Alarm and Remote Monitoring**:
- Many two-wire ultrasonic level meters have liquid level alarm
function, which can send out signals in time to remind operators to
deal with it. At the same time, modern versions of level meters
also support remote monitoring, which is convenient for remote
management and control.
Working Principle:
- Two-wire ultrasonic level meter uses the propagation principle of
ultrasonic wave for measurement. When the device transmits an
ultrasonic signal, the signal propagates to the liquid surface or
material surface and is reflected back. The height of the liquid
level is calculated based on the time taken for the ultrasonic wave
to be transmitted and received, combined with the sound velocity.
The sound velocity changes according to the temperature, pressure
and dielectric constant of the medium, so it is usually necessary
to compensate for these factors to improve the measurement
accuracy.
Advantages:
- **Low cost**: The two-wire design reduces the complexity of
installation and wiring, thereby reducing overall costs.
- **Easy installation**: The two-cable connection method makes
installation easier than traditional four-wire devices.
- **Remote adjustment**: Many two-wire ultrasonic level meters can
support remote adjustment and configuration, which is convenient
for on-site operation.
Applications:
- **Water industry**: Used for liquid level monitoring during
sewage and wastewater treatment.
- **Petrochemical**: Liquid level measurement in oil tanks and
chemical storage tanks.
- **Food and beverage**: Suitable for storage and level control of
liquid food and beverages.
- **Environmental protection industry**: Monitor liquid level
changes in different treatment pools.
Notes:
1. **Environmental factors**: The measurement of ultrasonic level
meters may be affected by environmental factors such as
temperature, humidity and pressure, and requires proper
calibration.
2. **Reflective surface**: The liquid surface should be smooth.
Foam, steam, etc. may affect the reflected signal and cause
measurement errors.
3. **Obstacles**: The ultrasonic transmitter and receiver of the
level meter should be protected from dirt or sediment, otherwise
the measurement accuracy will be affected.
The advantages of the two-wire ultrasonic level meter are its simple wiring and low cost, but it is also necessary to consider the above environmental factors and limitations in actual use to ensure accurate measurement.
Description
Ultrasonic liquid level gauge is a digital liquid level instrument controlled by a microprocessor. In the measurement, the ultrasonic pulse is emitted by the sensor (transducer). The sound wave is reflected by the liquid surface and is received by the same sensor or ultrasonic receiver. It is converted into an electrical signal through a piezoelectric crystal or magnetostrictive device, and is transmitted and received by the sound wave. time to calculate the distance from the sensor to the surface of the liquid being measured. Due to the non-contact measurement, the measured medium is almost unlimited and can be widely used to measure the height of various liquid and solid materials.
Multi-pulse low-voltage multi-point transmitting circuit,
double-balanced noise suppression multi-point receiving circuit
It improves the reliability of the instrument, solves the problem
of inaccurate measurement of uneven material levels, and greatly
enhances the anti-interference ability, allowing it to work stably
near the transmission tower of the substation.
Automatic power adjustment, gain control, temperature compensation.
Yingling's detection technology and rich software functions are
suitable for various complex environments.
Waveform calculation technology improves the measurement accuracy
of the instrument.
The interference echo suppression function ensures the authenticity
of the measurement data.
16-bit D/A conversion improves the accuracy and resolution of
current output.
The sensor is made of tetrafluoroethylene material and can be used
in various corrosive situations.
Multiple output forms: programmable relay output, high-precision
4-20mA current output, Rs-485 digital communication output, split
ultrasonic liquid level probe.
Specification
Main parameters of integrated ultrasonic liquid level meter
Measuring range | 0-3, 5, 8, 10, 15, 20, 30, 40, 50 100m |
Accuracy | 0.25% |
blind spot | 0.15-0.7m |
Operating temperature | -20℃-+60℃ |
pressure range | -1-16kg |
power supply | 24VDC, 220VAC |
output | 4-20mA, Rs-485 |
control | Two-way relay |
Protection level | IP68 |
Display method | 12864 dot LCD display |
Main parameters of corrosion-resistant sensor housing type split-type ultrasonic liquid level meter
Measuring range | 0-3, 5, 8, 10, 15, 20m, 30, 40, 50, 60, 70m |
Accuracy | 0.25% |
blind spot | 0.15-1.2m |
Operating temperature | Transmitter-20℃-55℃ Sensor-25℃-80℃ |
pressure range | -1-16kg |
power supply | 24VDC, 220VAC |
output | 4-20mA, Rs-485 |
control | Four way relay |
Protection level | IP68 |
Display method | 12864-dot LCD display, corrosion-resistant sensor housing made of tetrafluoroethylene |
Technical indicators
Measuring range | 0.3~5m, 0.3~8m, 0.5~12m |
blind spot | <0.3m,<0.5 m |
launch angle | 12° Small display resolution: 1mm |
Accuracy | ±0.3%×range |
show | Four digits and eight segments: 0.5-inch LED |
working frequency | 20 KHz ~ 43.0KHz (varies depending on model specifications) |
Site settings | Calibration is completed through the level meter button: factory calibration, can be calibrated on site |
Analog output signal | 4~20mA load>300Ω; 0~5V; 1~5V |
digital output | RS485 (supports Modbus) NPN switch output |
Operating Voltage | DC12—24V power consumption<1.5W |
Dimensions | Φ83×145×M65 |
shell material | PP |
weight | 272g(5m); 410g(12m) |
Installation method | External straight pipe thread M65×1.5 |
Protection level | IP65 |
temperature | -10℃~60℃ |
Installation principle
When the ultrasonic liquid level meter is working, high-frequency
pulse sound waves are emitted by the transducer (probe) and are
reflected by the surface of the measured object (water surface).
The refracted reflected echo is received by the same transducer
(probe) and converted into an electrical signal. . The time between
pulse transmission and reception (the movement time of the sound
wave) is proportional to the distance from the transducer to the
object surface. The relationship between the sound wave
transmission distance S, the sound speed C and the transmission
time T can be expressed by the formula: S= CⅩT /2
When installing an ultrasonic liquid level meter, the blind zone
problem of the ultrasonic liquid level meter must be considered.
When the liquid level enters the blind zone, the ultrasonic
transmitter cannot measure the liquid level. Therefore, when
determining the measuring range of the ultrasonic liquid level
meter, a margin of 50 cm must be left. When installing, the
transmitter probe must be higher than the maximum liquid level. The
position is about 50 centimeters. Only in this way can the accurate
monitoring of the liquid level and the safety of the ultrasonic
liquid level meter be ensured.
In actual use, due to poor installation considerations, the liquid
level gauge was submerged in water, causing the liquid level gauge
to be completely damaged.
Features of SGM ultrasonic level meter
Low price, small size and light weight, it can be used for
non-contact level measurement of liquids and bulk solids in food,
chemical, semiconductor and other industries, and can be used for
remote level monitoring and pump control.
Attention should be paid to mechanical installation: the
installation should be perpendicular to the surface of the object
to be measured, avoid being used to measure foam objects, and avoid
being installed at a distance less than the blind zone distance
from the surface of the measured object (blind zone: each product
will have a standard, which will be known with the product) , it
should be considered that the beam avoids blocking materials and
does not meet the filling mouth and container wall. When detecting
large solid objects, the probe orientation should be adjusted to
reduce measurement errors.
Catalog
BTSL7100 | Ultrasonic level gauge | |||
model | A | One-piece two-wire system | ||
B | Integrated three-wire system | |||
C | Integrated four-wire system | |||
D | Split four-wire streamlined type | |||
E | Split four-wire standard type | |||
Range ratio | 4 | L=4m | ||
6 | L=6m | |||
8 | L=8m | |||
10 | L=10m | |||
12 | L=12m | |||
15 | L=15m | |||
20 | L=20m | |||
30 | L=30m | |||
40 | L=40m | |||
custom | L=…..m | |||
voltage | D | DC24V LCD liquid crystal display | ||
E | DC24V LED digital tube display | |||
A | AC220V LCD liquid crystal display | |||
Probe extension | **mm |
Packing & Delivery
FAQ
1. Q: What information need to be provided to choose the suitable
model?
A: Application field, Nominal pressure ,Medium & medium
temperture , Power supply , Output,
Flow range, Accuracy, Connection and other parameters.
2. Q: Are you a trade company or a manufacturer?
A: We are an ISO approved manufacturer specialized in level and
flow measuring instruments.
OEM & ODM service are available. Welcome to visit us in China.
3. Q: What is your MOQ?
A: To start our cooperation, sample order is acceptable.
4. Q: What is your delivery date for the Intelligent Mini Micro
Turbine Fuel Oil Diesel Flow Meter?
A: The delivery date is about 3-15 working days after receipt of
payment.
5. Q: What is your payment terms?
A: We support T/T, PayPal ,Western Union.
For mass production order, it is 30% deposit in advance and 70%
balance before shipment.
6. Q: Do you have a warranty for the Flow Meter?
A: Yes, we have the warranty of 12 months.