LIRUISI Modular Data Center Dual-Row Integrated Machine Room Dedicated
Product introduction:
Adopts high integration and high standard design, including cabinet, cold aisle, power supply and distribution, cooling, management and other five systems.
Product parameters:
Model LY-UM | 15- 90 |
phase | Three-phase four-wire input/three-phase four-wire output |
capacity | 90KW |
Power module capacity | 15KW |
Number of power modules that can be installed | 6 |
input | |
rated voltage | 3X380VAC/400VAC/415VAC (3 phase + N) |
Voltage range | 100% load 305 ~ 478 VAC ; < 70% load 208 ~ 304VAC |
Rated frequency | 50/60HZ (automatic selection) |
Frequency range | 40 ~ 70HZ |
Input power factor | 100% load > 0.99 ; 50% load >0.98 |
Current Harmonic Loss (THDi) | < 3% @100% load |
output | |
rated voltage | 3X380VAC/400VAC/415VAC (3 phase+N) |
Voltage stability (steady state) | ≤ 1% typical (balanced load); ≤ 2% typical (unbalanced load) |
Voltage stability (Shun state) | ≤ ± 5% typical value |
Rated frequency | 50/60HZ |
Frequency Range (Synchronous Correction Range) | 46 ~ 54HZ /56 ~ 64HZ |
Frequency range (battery mode) | 50/60 HZ士1% |
overload capacity | 110% 60 minutes, 120% 10 minutes, 150% 60 seconds, >150% 200ms |
Overload Capability Harmonic Distortion (THDV) | ≤ 1.5% THD (linear load) ; ≤ 4% THD (Nonlinear Load) |
efficiency | Up to 94.5% |
Battery/Charge | |
rated voltage | 216V (12VX36 pieces) |
Maximum voltage | 240V (12VX40 pcs) |
Lowest voltage | 192V (12VX32 pieces) |
float voltage | 2.25V / Cell |
High charging voltage | 2.35V / Cell |
temperature compensation | Yes. |
Maximum charging current | 6A |
physical properties | |
Dimensions: Width X Depth X Height (mm) | 600X1200X2000 |
295 | |
Use environment | |
temperature and humidity | 0-40" C ; 0-95% relative humidity (non-condensing) |
elevation | < 1000m rated power |
IP protection class | IP 20 |
Control management | |
Smart RS-232/USB | Supports Wind0WS@ 2000/2003/XP/ViSta/2008, Wind0WS@ 7/8, LinuX and MAC |
Optional SNMP | Power management Support SNMP management and network management |
safety standards | |
safety regulations | IEC/EN 60950-1; IEC/EN 62040-1 |
electromagnetic specification | IEC/EN 62040-2 Categ0ry C3 |